KEYPAD MESSAGES

The GEM-RP1CAe2/GEM-K1CA Keypads can display the below messages. The GEM-RP2ASe2/GEM-K2AS will display similar
abbreviated messages that may scroll through two screens. Note: See page 7 for a listing of the keypad specific User Guides avail-
able. These User Guides contain more details regarding the various keypad messages.

SYSTEM READY - All zones operating; system can be armed. 1

through 4 = Area.


ARMING YYY/XXX SECONDS - Exit delay in progress. XXX = exit

time remaining in 10-second decrements; YYY = AWAY or
STAY. Arming then becomes ARMED.


DISARM NOW/XXX SECONDS
- Entry delay in progress. XXX =

entry time remaining in 10-second decrements.


SYSTEM ARMED - Panel armed. GEM-RP1CAe2/GEM-K1CA

keypads only.


ZONE FAULTED
- One or more zones not secured. Display status

for zone description(s). GEM-RP1CAe2/GEM-K1CA only.


CAN'T ARM SYSTEM/ZONE FAULTED - Arming attempted with

Priority Zone in trouble. Secure zone to arm.


DAY ZONE TROUBLE - Trouble condition on Day Zone, followed

by one or more zone descriptions.


INVALID ENTRY/TRY AGAIN
- Wrong code/time/area number

entered.


CAN'T ARM SYSTEM/PRESS RESET KEY
- Arming attempted

with System Trouble present. Press the

C

button and then

arm the system.


ALARM - Alarm condition, followed by one or more zone

descriptions.


FIRE ALARM
- Alarm condition on a Fire Zone. Enter your code

then press the

U

or

D

button to silence the sounder. Correct

the cause of the alarm, then press the

C

button again. Fire

alarm condition, followed by one or more zone descriptions.


SYSTEM TROUBLE
- A System Trouble display will be followed by

one or more of the following error codes:

AC POWER FAIL/E01-00 SERVICE. Power failure. Check

power transformer. Check for blown fuse or circuit breaker;
general power outage.

LOW BATTERY/E02-00 SERVICE. Battery below 11 volts. If

not recharged within 24 hours, replace it.

COMM FAIL/E03-00 SERVICE. Unsuccessful communication

to central station. Note: Will also display if panel improperly
programmed to report; i.e., Report Alarm, Report Codes,
Subscriber ID Numbers, etc. must be programmed.

WIRELESS TROUBLE/04-NN SERVICE. Wireless transmitter

supervisory failure. NN = transmitter number.

WIRELESS LOWBATT/E05-NN SERVICE. Rf transmitter low

battery. NN = transmitter number.

SYSTEM TROUBLE/E06-NN SERVICE. Rf receiver response

trouble. NN = receiver number.

SYSTEM TROUBLE/E07-00 SERVICE. Download failure.
SYSTEM TROUBLE/E08-00 SERVICE. Telephone line failure

(system trouble displays after a fixed 60 second delay).

SYSTEM TROUBLE/E09-00 SERVICE, NO PANEL PROGRAM.

System cold start not programmed after address 2286.

SYSTEM TROUBLE/E10-NN SERVICE. Keypad response

failure. NN = keypad number.

SYSTEM TROUBLE/E11-NN SERVICE. Keypad tamper cover

removed. NN = keypad number.

SYSTEM TROUBLE/E12-NN SERVICE. Expansion zone

module failure. NN = module number.

SYSTEM TROUBLE/E13-NN SERVICE. EZM module cover

removed. NN = module number.

SYSTEM TROUBLE/E14-NN SERVICE. Relay board response

failure. NN = relay board number.

SYSTEM TROUBLE/E15-NN SERVICE. Wireless transmitter

tamper cover removed. NN = transmitter number.

SYSTEM TROUBLE/E16-NN SERVICE. Receiver jammed. NN

= receiver number.

SYSTEM TROUBLE/E17-NN SERVICE. Receiver cover

removed. NN = receiver number.

SYSTEM TROUBLE/E18-NN SERVICE. Key fob RF transmitter

low battery. NN = key fob transmitter number.

SYSTEM TROUBLE/E19-00 SERVICE. Internal user memory

error. Select RESET SYSTEM TBL. Press the

U

or

D

button, then the

C

button.

SYSTEM TROUBLE/E20-00 SERVICE. Internal dealer memory

error.

SYSTEM TROUBLE/E22-NN SERVICE. No trip detected on PIR

Supervision Zone within programmed Sensor-Watch time.
NN = Zone number. To reset, press NEXT/YES button at
“RESET SENSOR MSG” function display.

SYSTEM TROUBLE/E27-00 SERVICE. Printer Failure. Call

installing company for service.

SYSTEM TROUBLE/E39-00 SERVICE. Receiver capacity error.
SYSTEM TROUBLE/E40-00 SERVICE. RF Self-Test failure.
SYSTEM TROUBLE/E41-NN SERVICE. Trouble condition on a

Fire Zone. Press

C

button to silence the sounder.

Correct the trouble, then press the

C

button again.

SYSTEM TROUBLE/E51-00 SERVICE - Alarm Output

Supervisory.

SYSTEM TROUBLE/E99-00 SERVICE. Keypad Panic shorted

too long (RP2/K2 and RP3/K3 keypads).

NN OUT OF SYSTEM - Keypad inoperative. NN = keypad

number.

FAULT FIND/RF SIGNAL POWER - Fault-find Mode activated.