background image

www.schischek.com

RedMax actuators are equipped with a universal supply unit working at a voltage range

from 24 to 230 VAC/DC. The supply unit is self adjustable to the connected voltage!

The safety operation of the spring return function works if the supply voltage is cut.

For electrical connection inside hazardous areas an t erminal box, certificated in acc. with

ATEX is required (e.g. RedBox).

Electrical connection

PA

PA

U

0

= 10,6 V

I

0

= 11 mA

P

0

= 30 mW

C

i

= 0

L

i

= 0

IIC

IIB

IIA

C

0

830 nF 3,7µF 4,5 µF

L

0

2 mH

5 mH 10 mH

Schischek GmbH Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax ++49 (0)9101-908177, Email [email protected]

RedMax-5.10-BF

RedMax-15-BF

Special makes

RedMax-..-VA/-CT

E X P L O S I O N P R O O F

Error indication

Function, adjustment and parameter

Parameter, Adjustment - Failure indication

Wiring diagram RedMax-5.10-BF and RedMax-15-BF

Example: RedMax-5.10-BF

Requested parameter:

Torque 10 Nm

Running time motor 60 sec/90°

Result: switch position (S) 08

Parameter selection

Type

Torques

RedMax -5.10-BF u 5 Nm 10 Nm

RedMax- 15-BF u 15 Nm 30 Nm

q

q

Running times

Position of switch S

3 sec./90° u

00

05

15 sec./90° u

01

06

30 sec./90° u

02

07

60 sec./90° u

03

08

120 sec./90° u

04

09

On-off 1-wire- spring return + EEx-i circuit

1

2

°C

push button

EEx-i circuit for

passive + potential free

push button on site

and sagfety temperatur sensor

(Type FireSafe accessories)

6 7

Integrated aux. switches

max 24V/3A, 230V/0,5A

switching at 5° and 85°.

Supply at aux. switches must

be the same like supply of the

actuator on same fuse.

< 5 °

8

9 10

> 85

°

11

1

2

3

~

-

~

+

PE

heater

5

24...230 VAC/DC

FireSafe

4

On-off/3 pos - spring return + EEx-i circuit

1

2

°C

push button

EEx-i circuit for

passive + potential free

push button on site

and sagfety temperatur sensor

(Type FireSafe accessories)

6 7

Integrated aux. switches

max 24V/3A, 230V/0,5A

switching at 5° and 85°.

Supply at aux. switches must

be the same like supply of the

actuator on same fuse.

< 5 °

8

9 10

> 85 °

11

1

2

3

~

-

~

+

PE

heater

5

24...230 VAC/DC

FireSafe

4

! Attention !

If you use this type of

wiring the heater does

not work in case of

open contact.

a

b

EEx-i intrinsic safe data

If 3 sec. mode is selected, the self adju­

stment of Angle of rotation must be started

and operation mode of max. 10% ED

must be guaranteed.

Never use actuators in this mode without

external torque/force.

Attention!

!

!

Standard wiring = spring return in ~10 sec.

Additional wiring terminal 5 = spring return in ~ 3 sec.

Standard wiring = spring return in ~10 sec.

Additional wiring terminal 5 = spring return in ~ 3 sec.

Switch - Push button - Lamp

for adjustment,

behind the blancking plug

10-position switch (S)
Push button(T)

3-colour LED

B

A

B

S

T

A

See extra information “EL”

A) Self adjustment of Angle of rotation:

Switch (S) into position 02 (low torque) or 07 (high torque), then push button (T) for

minimum 3 seconds. The actuator will drive into both end positions to be adjusted.

LED indicates green.

Adjusmtent time needs approx. 60 sec. (30 sec. On, 30 sec. Off). After that, switch S

into position 00-09 in acc. with your required torque and running time.
B) Selection of running time and torque:

Put switch (S) into the correct/selected position in acc. to above table.

The selected parameter will work at next operation of the actuator.

Adjustment can be done even without supply voltage. If supply voltage is available turn

switch only if actuator is not running.
C) Running time spring return:

The running time of 3 or 10 sec. spring return is selected by wiring

(see wiring diagrams SB 7.0/7.1).
D) Additional information for 3-pos operation:

a closed, b open = direction I

b closed, a open = direction II

a and b closed = Motor doesn't work

a and b opened = Motor doesn't work

Direction (I and II) depends on left/right mounting of the actuator to the damper/valve.

You can change direction of the motor by changing electrical wiring terminal 3 and 4.
E) Function of a passive sensor in the EEx-i circuit:

If the sensor opens the EEx-i circuit the actuator runs into its safety end-position with

spring return

SB 7.0

SB 7.1