Error/Symptom

Reason

Solution

M.EZ-01.05-S-en-Zusatzinfo EL

2006-04-05

Schischek GmbH Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax ++49 (0)9101-908177, Email [email protected]

Actuator does not work

LED lights red

l The actuator is operated by a too high ambient

temperature and the internal temperature sensor

responded

l Shut off actuator and let temperature decrease, reduce ambient

temperature by suitable measures e.g. ventilation or other mounting

position of the actuator

02

Actuator does not work

LED lights green

l 3-Pos control signal is wired on both entrances
l Required torque is greater than actuators torque

l Control signals are not attached or attached on a

wrong conductor

l Actuator is incorrect mounted and is blocked by an

external stop unit

l Actuator is clocked with more than 20 impulses <0,5

per sec. and therefore adjusted into suspend mode

l Interchanged supply lines

l Readjust/correct circuit
l Adjust a higher torque at the actuator if possible otherwise exchange

for a type with higher torque.

l Examine rule and adjusting signal in accordance with attached diagram

l Dismount actuator and testdrive without load for operability. Install

actuator accordingly that the power transmissions runs without external

blockade or torsion

l Switch off supply voltage for at least 2 sec. thereby a reset is conducted

Readjust controller in order to extend control pulses

l Wire 1 must be (-, N) and wire 2 (+, L)

03

Spring return funktion is 10 sec./90°,

should however amount to 3 sec./90°

l Bridge 2 --5 is not established

l Bridge conductor 2 of the constant voltage supply with conductor 5

05

Spring return funktion is 3 sec./90°,

should however amount to 10 sec./90°

l Bridge 2 --5 is established

l Disconnect bridge

06

Actuator does not start after more than

2 briefly following adjusting functions

in the 3 sec. mode where set

l The maximal permissable cyclic duration of 10%

ED was not complied to, the actuator is in a safety

disconnection mode

l Wait approx.1 minute until internal electronics cool down to operating

temperature.

07

Y-drive in the 3-pos mode can not gear

into intermediate positions

l The conversion of constant mode on 3-pos-modus

was not set

l Recalibrate the actuator in accordance with assembly instructions

08

Actuator sits diagonally on the squared

damper shaft

l The actuators have an angle of rotation of 95°

inclusive 5° pre-tention. While assembling the pre-

loading was not considered

l Dismount actuator of the damper, use the enclosed socket wrench to

draw up approx. 5° over the hand operated control device before

remounting on the damper shaft. Consider additional information ME

of the assembly instructions

09

Actuator is with clamp stand KBS

actuated installed onto damper shaft

and does only partly or not at all drive

l Provided that the electrical basic conditions specified

above are fullfilled, the anti- twist plate could be so

installed that the actuator blocks itself due to the

twisted and not centric shaft connection and therefore

interlocks

l Loosen the anti-twist plate and remount that the actuator can implement

an easy oscillationg motion over its angle of rotation

10

A modulating actuator (Y) works with

reduced angle of rotation and already

reaches its end positions before O V/4

mA, respectively before 10V/20mA.

l At start up no self adjustment of angle of rotation

was accomplished

l Accomplish self adjustment of angle of rotation in accordance with

assembly instruction

11

LED flashes irregularly and actuator

does not work

l Actuator does not receive sufficient supply voltage

l Cable to long, voltage drop in the supply line to large

l Increase line cross section or increase tension at the transformer/power

suply unit

l Increase line cross section or increase tension

12

l No power supply attached
l The actuator is operated beyond ex-prevention

ambient temperature specifications and the internal

temperature sensor did irreversibly shut down

operations

l Attache power supply and turn on
l Because of inadmissable operation the actuator drove out of safety

relevant reasons into an irreversible condition and must be exchanged.

Accompanying new installation the ambient temperature has to be

reduced accordingly

Actuator does not work

LED does not lights

01

Acuator does not work

LED is red blinking

04

l The actuator has been mounted by temperatures

of less than -20°C and did not reach is operating

temperatur of at least -20°C.

l Ensure that a constant voltage supply on conductor 1--2 is existing.

l Wait until the required operating temperature is achieved by the actuators

internal heating system.The actuator will start operating independently

ExMax-.. and RedMax-.. extra information EL - size S

E X P L O S I O N P R O O F