Help, Changing passwords – Raritan Computer PCS12 User Manual

Page 29

Advertising
background image

C

HAPTER

4: O

PERATION AND

C

ONFIGURATION

19

Reboot

Type REBOOT n at the PCR8> prompt and press the <Enter> key to reboot or reset equipment attached to Outlet “n.” When
the REBOOT command is sent from the prompt, the Remote Power Control unit powers OFF the corresponding outlet for
approximately 10 seconds, and then powers it ON again. If all outlets are powered OFF, they will be powered ON again in
sequence.

Note: This command works only on outlets that were “ON” prior to executing the Reboot command.

Important! Typing ON 0 (zero), OFF 0, or REBOOT 0 at the command prompt causes the Remote Power
Control to turn ON, OFF, or REBOOT ALL outlets. Entering a 0 (zero) indicates that the command should be
executed for ALL outlets.

Help

Type HELP at the prompt and press the <Enter> key to view a list of commands and functions for the Remote Power Control
unit. These commands can be typed at the Status menu prompt at any time:

Note: <cr> indicates a carriage return or <Enter>


Changing Passwords

When the Remote Power Control unit leaves the factory, no password is programmed; the password field is blank. Once a
password is programmed, the Remote Power Control unit requires password entry before allowing a user to execute any
commands.

Type Password at the PCR8> prompt and press the <Enter> key. Enter the new Password, then re-enter the new Password for
confirmation, and press the <Enter> key. Once a password is in place, it will be required to issue commands to the Remote
Power Control unit in the future.

Important! Passwords are case sensitive.

PCR8>help

On n <cr>

--Turn on an Outlet, n=0,1...8,all

Off n <cr>

--Turn off an Outlet, n=0,1...8,all

Reboot n <cr>

--Reboot an Outlet, n=0,1...8,all

Status <cr>

--PCR8 Status

Config <cr>

--Enter configuration mode

Lock n <cr>

--Locks Outlet(s) state, n=0,1...8,all

Unlock n <cr>

--Unlock Outlet(s) state, n=0,1...8,all

Current <cr>

--Display True RMS Current

Clear <cr>

--Reset the maximum detected current

Temp <cr>

--Read current temperature

Voltage <cr>

--Display True RMS Voltage

Logout <cr>

--Logoff

Logoff <cr>

--Logoff

Exit <cr>

--Logoff

Password <cr>

--Changes the current user password

Whoami <cr>

--Displays the current user name

Unitid <cr>

--Displays the unit ID

Help <cr>

--This Command

Enter new Password>*****
Re-Enter new Password>

Advertising
This manual is related to the following products: