Displays the maximum water temperature

for the boiler. Range is determined by

screen number 23. Factory default is

180°F (82.2°C) Maximum.

Screen number

Displays the minimum water temperature

for the boiler. Range is determined by

screen number 23. Factory default is

105°F (40.5°C) Minimum.

9

0

F

F

O

T

U

C

R

O

O

D

T

U

O

T

E

M

P

X

X

X

.

X

°

F

The outdoor cut-off sets the maximum outdoor temperature at which heat is desired. This control sets the

outdoor temperature above which the boiler bank is disabled. If the outdoor temperature increases beyond the

outdoor cut-off setting, there is no call for heat and the pump turn off delay becomes active. If the outdoor

temperature falls below the outdoor cut-off minus the outdoor cut-off Deadband the boiler bank will again be

enabled.

The Outdoor cut-off Temperature is from 32°F to 200°F (0°C to 93.3°C).

Recommended Initial Setting for outdoor cut-off Temperature is 75°F (23.8°C).

Factory default is 75°F (23.8°C).

Screen number

Fahrenheit or Celsius

0

1

F

F

O

T

U

C

R

O

O

D

T

U

O

D

E

A

D

B

A

N

D

X

X

.

X

°

F

Outdoor Cut-Off Deadband:

Screen number

The Outdoor cut-off deadband sets the number of degrees below the outdoor cut-off where the outdoor cut-off

reset occurs. The outdoor cut-off deadband limit is -1 degree F to -10 degrees F. Default is -3 degrees F.

Fahrenheit or Celsius

Note: This parameter can only be set in °F, but will display in °C if °C is chosen.