Raypak Y-200 User Manual

Page 28

Advertising
background image

28

Password:

9

1

D

R

O

W

S

S

A

P

A

A

A

Screen number

Used by maintenance personnel to change settings.

0

2

P

U

T

E

S

T

I

N

U

M

A

S

T

E

R

P

B

S

B

S

B

S

S

S

A

A

A

Screen number

In display mode shows AAA or current password.

To enter the password:

1.Push the mode key. The cursor under the first A should start flashing.

2.Change the first letter by using the up or down key to the desired letter. Use the right key to go to

the next letter and change it with the up or down key. Do the same to the last letter then push the

mode key when done.

• If the password is valid, the screen will allow the user to change to the first setup screen.

Setup:

P=

SYSTEM PUMP MODULE

Rule: Always on before boiler. Always off after last boiler off + programmed delay.

P is relay #1 as supplied.

B=

INDICATES BOILER

Rule: Always B before S

S=

INDICATES BOILER STAGE

Rule: Must have "B" for that boiler ON and prior stages ON for that boiler.

A=

AUXILIARY RELAY MODULE

Optional:

A1 - User defined function. (i.e. powered louvers, boiler pump, draft fan)

A2 - User defined function. (i.e. alarm light)

A3 - User defined function. (i.e. alarm bell)

NOTE: Piezo-electric alarm horn can be silenced by pressing the "MODE" switch.

Table J: Definitions