Boiler Turn-Off Delay

In a multiple boiler system: The boiler Turn-Off Delay
sets the amount of delay before each additional boiler
is turned off. This delay starts when the preceding boil-
er is turned off.

The Boiler Turn-Off Delay range is from 0 to 600 sec-
onds.

Recommended Initial setting for Boiler Turn-Off Delay
is 30 seconds.

Factory default is 30 seconds.

Stage Turn-Off Delay

The Stage Turn-Off Delay sets the time delay before a
stage in a multi-stage boiler configuration is turned off.
This delay starts when the stage or boiler preceding
the next stage is turned off.

The Stage Turn-Off Delay range is from 0 to 600 sec-
onds.

Recommended Initial setting stage for Turn-Off Delay
is 10 seconds.

Factory default is 10 seconds.

6

1

D

R

A

D

N

A

T

S

Screen number

Proportional Integral Derivative (PID):

Standard:

This is the factory default screen.

Standard mode is controlled by:
Screen 3: Control Band
Screen 14: Time On Delay
Screen 15: Time Off Delay

Screen number

P I D C = X X X S = X X 1 6

P = X X X D = X X X I = X X X

NOTE: PID mode is the logic control for the micro-

processor; disables screens 3, 14 and 15.