Branch circuit sizing and wire size guide, Electrical connections – Rheem Warrior Series AP10414-9 User Manual

Page 9

Advertising
background image

9

Branch Circuit Sizing and Wire Size Guide

Total Water

Recommended Over Current Protection

Copper Wire Size AWG Based

Heater Wattage

(fuse or circuit breaker amperage rating)

on N.E.C. Table 310-16 (75°C)

120V

208V

240V

120V

208V

240V

1500*

20

15

15

12

14

14

1700

20

15

15

12

14

14

2000

25

15

15

10

14

14

2500

30

15

15

10

14

14

3000

35

20

20

8

12

12

3500

25

20

10

12

3800

25

20

10

12

4000

25

25

10

10

4500

30

25

10

10

5000

30

30

10

10

5500

35

30

8

10

6000

40

35

8

8

9000

50

8

*Less than 1500 watts may be wired 14 gauge with 15 amp protection. Check Local Electrical Codes, as they will also apply.

NOTICE: This guide recommends minimum branch circuit sizing and wire size based on National Electric Code. Refer to
wiring diagrams in this manual for field wiring connections.

CAUTION: The presence of

water in the piping and water
heater does not provide
sufficient conduction for a
ground. Non-metallic piping,
dielectric unions, flexible
connectors etc. can cause the
water heater to be electrically
isolated.

Electrical Connections

A separate branch circuit with copper
conductors, overcurrent protective device
and suitable disconnecting means must be
provided by a qualified electrician.
All wiring must conform to local codes or
latest edition of National Electrical Code
ANSI/NFPA 70.
The water heater is completely wired to
the junction box inside jacket at the top
front of the water heater. An opening for
1/2

″ or 3/4″ electrical fitting is provided

for field wiring connections.
The voltage requirements and wattage load
for the water heater are specified on the
rating plate on the front of the water heater.

The branch circuit wiring should include
either:

Metallic conduit or metallic sheathed
cable approved for use as a grounding
conductor and installed with fittings
approved for the purpose.
Non-metallic sheathed cable, metallic
conduit or metallic sheathed cable
not approved for use as a ground
conductor shall include a separate
conductor for grounding. It should be
attached to the ground terminals of
the water heater and the electrical
distribution box.

WARNING

WARNING

Water heater junction box.

Ground screw

Junction

box cover

Wire connections

Conduit

connector