Installation, Minimum alcove clearance to combustible materials – Regency ALTERRA CS1200 User Manual

Page 8

Advertising
background image

8

Regency CS1200 Freestanding Wood Stove

INSTALLATION

Z

6"

6"

16"

Y

Y

X

X

6"

for

angled

corners

6"

16"

6"

6"

Z

The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.

Note: Minimum alcove ceiling height - 84"

Maximum depth of alcove - 36"

Minimum Overall Width (X) of Floor
Protector
for all installations:

US

38-3/4"

Canada

42-3/4"

Floor Protection

A combustible fl oor must be protected by a non-combustible material (like tile,
concrete board, or certifi ed to UL-1618 or as defi ned by local codes) extending
beneath the heater and a minimum of 6" from each side and minimum 16" from
the fuel door opening of the stove and minimum 6" (or the rear clearance to
combustibles whichever is smaller) from the rear of the stove.

NOTE: In Canada, fl oor protection must extend 18" to the front and 8" to each side of the stove.

Minimum Alcove Clearance to Combustible Materials

Unit

From Back Shield

+ Side Shields.

From Flue

Center-Line

Min.

Width

Min. Hearth
to Rear Wall

CS1200

G

H

I

J

K

L

11"

7"

24-1/2"

14-1/2"

49-1/8"

39-1/4"

Minimum Overall Depth (Y) of Floor Protector

Unit

Residential

"C" Vent

Residential

Close Clearance

Mobile Home

Close Clearance

Alcove

CS1200

Y

Z

Y

Z

Y

Z

Y

Z

USA

39"

6"

39

6"

39"

6"

39"

6"

Canada

43"

8"

43"

8"

43"

8"

43"

8"

MINIMUM ALCOVE CLEARANCE TO COMBUSTIBLE MATERIALS

MEASUREMENTS "FROM UNIT" ARE FROM THE SIDE SHIELDS OF THE STOVE TO A SIDE WALL OR TO A CORNER, AND

FROM THE REAR HEAT SHIELD TO A BACK WALL