RV53i & RV53e Operation and Installation Manual

Additional Clearances

Local codes supersede these clearances.

Avoid termination locations near a dryer vent.

Avoid termination locations near commercial cooking exhaust.

60"

V

V

(1.52 m) between
Rinnai terminals
at different levels

12"

12"

36"

INSIDE

CORNER

V

V

(0.91 m) to ventilated
or unventilated soffit
or eve vent; or to a
deck or porch

(0.30 m ) to an
inside corner

(0.30 m) between
Rinnai terminals at
same level

24"

V

(0.61 m) to wall or parapet

(0.30 m) between
Rinnai terminals at
same level

12"

V

V

(1.52 m) vertically
between Rinnai terminals

V

60"

V

Vent terminal (represents
concentric vent terminal)

2"

36"

12"

IN SID E

C O R NER

(0.91 m) to ventilated
or unventilated soffit
or eve vent; or to a
deck or porch

50 mm)
between Rinnai
terminals at
same level

RV53i

RV53
e