Warning – Roberts Gorden Linear Heater User Manual

Page 10

Advertising
background image

BH-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

24

SECTION 7: OPTIONAL HEATER ACCESSORIES

7.1 U-Tube Configuration

Heaters (except BH-40) are approved for optional
U-tube configurations.
The U-tube may be installed in either a standard
horizontal position, a 45° position or in an opposite
45° position as shown on Page 6, Figure 7 through
Page 7, Figure 9
. When using a U-tube configuration,
the following additional rules must be adhered to:

• A minimum of 10' (3 m) on BH-60/80 and a

minimum of 15' (4.5 m) on BH-100/115/125/140/
150/175/200 is required between the burner and
the U-tube.

• The correct turbulator (See Page 20, Step 6.4)

must be installed in the last standard section of
the tube.

• The burner must never be operated in a tilted

position.

• The heater must be properly supported at all

locations. See Page 26, Figure 19.

WARNING

Cut/Pinch Hazard

Wear protective gear during installation,
operation and service.

Edges are sharp.

Failure to follow these instructions can result
in injury.