5

SIZING OF D2 COPPER DISCHARGE PIPE FOR COMMON TEMPERATURE RELIEF VALVE OUTLET SIZES

MAXIMUM RESISTANCE

ALLOWED, EXPRESSED AS A

LENGTH OF STRAIGHT PIPE

(I.E. NO ELBOWS OR BENDS)

MINIMUM SIZE OF

DISCHARGE PIPE (D2)

FROM TUNDISH

MINIMUM SIZE OF

DISCHARGE PIPE

(D1)

VALVE

OUTLET

SIZE

RESISTANCE
CREATED BY

EACH ELBOW

OR BEND

up to 9m

up to 18m

up to 27m

up to 9m

up to 18m

up to 27m

up to 9m

up to 18m

up to 27m

22mm

28mm

35mm

28mm

35mm

42mm

35mm

42mm

54mm

15mm

22mm

28mm

G

1

/

2

G

3

/

4

G1

0.8m

1.0m

1.4m

1.0m

1.4m

1.7m

1.4m

1.7m

2.3m

GUIDANCE NOTES - TYPICAL DISCHARGE PIPE ARRANGEMENT

SAFETY DEVICE

(e.g. TEMPERATURE RELIEF VALVE)

500mm MAXIMUM

300mm

MINIMUM

TUNDISH

FIXED GRATING

METAL DISCHARGE PIPE (D1)

FROM TEMPERATURE RELIEF

TO TUNDISH

METAL DISCHARGE PIPE (D2)

FROM TUNDISH,

WITH CONTINUOUS FALL

(SEE 3.9d i-iv & TABLE 1)

DISCHARGE BELOW

FIXED GRATING

(3.9d GIVES ALTERNATIVE POINTS

OF DISCHARGE)

TRAPPED GULLY

New Stainless imp_alt 2/15/05 12:15 PM Page 6