Roberts Gorden CTH2-125 User Manual

Page 41

Advertising
background image

SECTION 8: V

ENTING

35

8.3 Horizontal Venting

In noncombustible walls only, vent terminal
(P/N 02537801-1P) may be used.

For 4'' (10 cm) vents in either combustible or
noncombustible walls, use Tjernlund VH1-4 (P/N
90502100) or equivalent insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.

For 6'' (15 cm) common vents in either combustible
or noncombustible walls, use Tjernlund VH1-6 (P/N
90502101) or equivalent insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.

8.4 Vertical Venting

For 4'' (10 cm), an approved vent cap
(P/N 90502300) must be used.
For 6'' (15 cm) common vent, an approved vent cap
(P/N 90502302) must be used.
For common vertical venting of more than two
heaters, See Page 37, Section 8.10.
A vent shall not extend less than 2' (.6m) above the
highest point where it passes through a flat roof of a
building.

8.5 Unvented Operation Tube Termination

Turndown type vent terminal with a screen must be
installed at the exhaust end of the tube. Vent terminal
design shall not incorporate backdraft flap.

FIGURE 22: Tube Termination

8.6 Length Requirements

The maximum vent length allowed is 45' (13.7 m).
The maximum outside air supply duct length allowed
is 45' (13.7 m).

The total vent length, plus outside air duct length,
plus any extensions to minimum heat exchanger
lengths, cannot exceed 65' (19.8 m).

Vent length should be limited to less than 20' (6 m). If
using vent lengths greater than 20' (6 m),
condensation will form in the vent pipe. Insulation
and additional sealing measures (high temperature
silicone at all seams) are required. Optional heat
exchanger beyond minimum lengths is considered as
vent length for length determination.

Subtract 15' (4.6 m) of maximum allowed vent or duct
length per vent elbow if more than two are used.

8.7 Horizontal Ventilation 4" (10 cm) Pipe

4" (10 cm)

Single Wall Pipe

Vent Adapter

Vent Terminal

Combustible or

Non-Combustible Wall

Vent Adapter

18" (46 cm)

Min.

Vent Terminal

4" (10 cm) Single Wall Pipe

Non-Combustible Wall Only

SIDE VIEW

Description

Part Number

Vent Terminal (Comb. Wall)

90502100

Vent Terminal

02537801-XX

Advertising
This manual is related to the following products: