SECTION 12: T

ROUBLESHOOTING

49

12.1 Honeywell SmartValve

®

II Troubleshooting

This heater is supplied with the Honeywell Smart-
Valve

®

II control system. This system is equipped with

a diagnostic function that will assist in performing
troubleshooting. The LED (Light Emitting Diode) indi-
cator at the top of the SmartValve

®

II control will flash

in various patterns to indicate status. The LED status
indication chart provided below gives a summary of
possible faults.

LED Status

Indicates

Off

No power to the control

Bright-Dim

Normal Operation.This indication

shows whenever the system is pow-
ered, unless some abnormal event
has occurred.

2 Flashes

Pressure switch remains closed lon-

ger than 30 seconds after a call for
heat begins (pressure switch stuck
closed). The SmartValve

®

II checks

the status of the pressure switch con-
tacts and must see a change in the
contact with every firing cycle. Placing
a jumper at the switch out of
sequence will result in a fault, with the
LED indicator flashing 2 times.

3 Flashes

Pressure switch remains open longer

than 30 seconds after combustion air
blower is energized. Check for correct
blower operation, blower intake
obstructions, pressure switch tubing
and wiring.

4 Flashes

Limit string open, 2" white jumper wire

on valve is loose.

5 Flashes

Flame signal sensed out of proper

sequence.

6 Flashes

System Lockout. Flame sensing cir-

cuit is not functioning properly. Per-
form the checks following the "Does
the burner stay lit?" bubble in the trou-
bleshooting flow chart on Page 50,
Section 12.2
.

Page 52, Section 12.3 will provide the information
needed to test the manifold gas pressure setting.
Page 50, Section 12.2 will guide you through several
troubleshooting steps to determine possible prob-
lems with the systems.

WARNING

Electrical Shock Hazard

Do not disconnect ground leads inside heater.

Do not interchange grounded and ungrounded
leads on transformer or ignition module.

Failure to follow these instructions can result
in death or electrical shock.