The weight of the vent stack or chimney must not rest
on heater draft hood. Support must be provided in
compliance with applicable codes. The heater top and
draft hood must be readily removable for maintenance
and inspection. Vent pipe should be adequately sup-
ported to maintain proper clearances from combustible
construction.

Type "B" double wall or equivalent vent pipe is recom-
mended. However single wall metal vent pipe may be
used as specified in the latest edition of the National
Flue Gas Code ANSI Z223.1.

For connections to gas vents or chimneys, vent instal-
lations shall be in accordance with Part 7, Venting of
Equipment, of the National Fuel Gas Code, ANSI
Z223.1, or applicable provisions of the local building
codes.

5' MIN

2' MIN

10' OR LESS

2' MIN

VENT CAP

VENT PIPE

DRAFT HOOD

HEATER

Fig. 10: Venting Minimum Clearances

Common Vents

Manifolds that connect more than one heater to a com-
mon chimney must be sized to handle the combined
load. Consult available guides for proper sizing of the
manifold and the chimney. At no time should the area
be less than the area of the largest outlet.

At the time of removal of an existing heater, the follow-
ing steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances remain-
ing connected to the common venting system are not
in operation.

(a) Seal any unused openings in the common venting

system.

(b) Visually inspect the venting system for proper size

and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe
condition.

(c) Insofar as is practical, close all building doors and

windows and all doors between the space in which
the appliances remaining connected to the com-
mon venting system are located and other spaces
of the building. Turn on clothes dryers and any
appliance not connected to the common venting
system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will oper-

WARNING: These heaters must not be connected
into any portion of mechanical draft systems
operating under positive pressure. To do so may
cause the flue products to be discharged into the
living space causing serious health injury.

Drafthood

Heater

Fig. 11: Common Venting