1) Adjust inlet gas pressure as

shown on rating plate.

2) Clean pilot orifice.
3) Replace thermocouple.

1

) Adjust manifold pressure as

shown on rating plate.

2) Clean burners free of debris or

insects.

3) Clean gas line or increase gas line

piping.

1) Refer to installation instructions

regarding combustion air
requirements.

2) Refer to installations instructions.
3) See yellow flame section above.

3)Pilot Outage.

(Standing pilot models)

4)Yellow lazy flame.

5)Sooting

1) Too low or too high gas

pressures.

2) Restricted pilot.
3) Weak thermocouple.

1

) Too low gas pressure.

2) Restricted burner intake ports.

3) Restricted gas line.

1) Insufficient combustion air.

2) Improper venting.
3) Severe yellow burner flames.