Gas piping – Rinnai R98LSI User Manual

Page 19

Advertising
background image

VB Series Indoor LS Manual

19

Pipe Sizing Procedure - Example

1. For some tables, you will need to determine the cubic feet per hour of gas required by dividing the gas input

by the heating value of the gas (available from the local gas company). The gas input needs to include all gas
products at the location and the maximum BTU usage at full load when all gas products are in use.

Gas

Input

of

all

gas

products

(BTU

/

HR)

Cubic Feet per Hour (CFH) =
Heating

Value

of

Gas

(BTU

/

FT

3

)

2. Use the table for your gas type and pipe type to find the pipe size required. The pipe size must be able to

provide the required cubic feet per hour of gas or the required BTU/hour.

Example: The heating value of natural gas for your location is 1000 BTU/FT

3

. The gas input of the RL94i is

199,000 BTU/HR. Additional appliances at the location require 65,000 BTU/hr. Therefore the cubic
feet per hour = (199,000 + 65,000) / 1000 = 264 FT

3

/HR. If the pipe length is 10 feet then the 3/4 inch

pipe size is capable of supplying 264 FT

3

/HR of natural gas.

Gas Piping

The gas supply must be capable of handling the entire gas load at the location. Gas line sizing is based on gas
type, the pressure drop in the system, the gas pressure supplied, and gas line type. For gas pipe sizing in the
United States, refer to the National Fuel Gas Code, NFPA 54. For Canadian gas pipe sizing, refer to the Natural
Gas and Propane Installation Code CAN/CSA B149.1. The below information is provided as an example. The
appropriate table from the applicable code must be used.

Pipe Size (inches)

3/4

1

1 1/4

1 1/2

10

273 514 1060

1580

20

188 353 726 1090

30

151 284 583 873

40

129 243 499 747

50

114 215 442 662

60

104 195 400 600

70

95 179 368 552

80

89 167 343 514

90

83 157 322 482

100

79 148 304 455

125

70 131 269 403

150

63 119 244 366

175

58 109 224 336

200

54 102 209 313

Length

Length

Pipe Size (inches)

1/2 3/4 1 1

1/4

10

291 608 1150

2350

20

200 418 787 1620

30

160 336 632 1300

40

137 287 541 1110

50

122 255 480 985

60

110 231 434 892

80

101 212 400 821

100

94 197 372 763

125

89 185 349 716

150

84 175 330 677

175

74 155 292 600

200

67 140 265 543

Pipe Sizing Table - Natural Gas

Pipe Sizing Table - Propane Gas

Inlet Pressure: less than 2 psi (55 inches W.C.)
Pressure Drop: 0.3 inches W.C.
Specific Gravity: 0.60

Inlet Pressure: 11.0 inches W.C.
Pressure Drop: 0.5 inches W.C.
Specific Gravity: 1.50

Schedule 40 Metallic Pipe

Capacity in cubic feet per hour

Schedule 40 Metallic Pipe

Capacity in Thousands of BTU per Hour