Rinnai R98LSI User Manual

Page 30

Advertising
background image

30

VB Series Indoor LS Manual

24"

V

Additional Clearances - Vent Terminal

Local codes supersede these clearances.

Avoid termination locations near a dryer vent.

Avoid termination locations near commercial cooking exhaust.

For VA3237 air intake position, follow the ANS Z21.10.3 ● CSA 4.3 requirements on the previous page.

60"

V

V

(1.52 m) between
Rinnai terminals
at different levels

12"

12"

36"

INSIDE

CORNER

V

V

(0.91 m) to ventilated
or unventilated soffit
or eve vent; or to a
deck or porch

(0.30 m ) to an
inside corner

(0.30 m) between
Rinnai terminals at
same level

(0.61 m) to wall or parapet

(0.30 m) between
Rinnai terminals at
same level

12"

V

V

(1.52 m) vertically
between Rinnai terminals

V

60"

V

Vent terminal (represents concentric vent terminal or VA3237 exhaust only vent terminal)

Advertising
This manual is related to the following products: