Troubleshooting – Raypak RAYTHERM P-926 User Manual

Page 32

Advertising
background image

32

IMPORTANT NOTICE
These instructions are primarily intended for the use of qualified personnel specifically trained and experienced
in the installation of this type of heating equipment and related system components. Installation and service
personnel may be required by some states to be licensed. Persons not qualified shall not attempt to install this
equipment nor attempt repairs according to these instructions.

MECHANICAL (FOR QUALIFIED SERVICE PERSONNEL ONLY)

PROBLEM

Harmonics, or whining noise

Heater going on and off
continously

Liming or scale forming on
heat exchanger

Sooting

Pilot outage

Yellow lazy flame

U.G. Inoperative……………………

*Debris or restriction in system……

*Debris in gas line…………………..
Lowflow……………………………...

Dirty filter……………………………
Low water level in pool..……………
External bypass setting out of
adjustment…………………………..
*Pressure switch out of
adjustment…………………………..

Pool water…………………………....

High flow rates…………………….....

U.G. Inoperative……………………..

*Air starvation………………………..
*Improper venting…………………....

*Insects or debris clogging
burner intake ports…………………..

Low gas pressure…………………....
Restricted pilot……………………....
Weak pilot generator………………..

Low gas pressure…………………....
*Insects or debris clogging
burner intake ports…………………..

Check movement by putting in hot
water (110°F or higher). If no move-
ment, replace.
Locate the restriction and remove.
Flush system and clean.
Remove debris or blow out gas line.
Scale forming in heat exchanger -
clean heat exchanger and check
pool pH and total alkalinity.

Backwash filter.
Raise water level.

Adjust bypass

Adjust pressure switch

Recommended pH should be be-
tween 7.3 and 7.8 total alkalinity 100-
150 PPM maximum. Hardness -150-
400 PPM maximum. (see page 2)

Reduce by adding manual bypass
valve and adjust by putting ther-
mometer in header (1/4" NPT) drain
opening. Set bypass so thermome-
ter reads between 105° and 110°F.
Check movement by putting in hot
water (110°F or higher). If no move-
ment, replace.
Refer to installation instructions.
Follow recommended installation
instructions.

Clean burners

Adjust gas pressure.
Clean pilot.
Replace pilot.

Adjust gas pressure.

Clean burners.

CAUSE

SOLUTION

*Usually occurs on initial start-up

TROUBLESHOOTING

Advertising
This manual is related to the following products: