In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code

2

In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code

+

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single
family dwellings and serves both dwellings.

** Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the

floor.

*

For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, one of the following shall be
indicated:
a) A minimum clearance value determined by testing in accordance with section 4.7.3, 6.5.5, 8.5.5; or;
b) A reference to the following footnote:

"Clearance in accordance with local installation codes and the requirements of the gas supplier."

H

Clearance to each
side of center line
extended above
meter/regulator
assembly

3' (91 cm) within a height 15' (4.5 m) above

the meter/regulator assembly

*

I

Clearance to
service regulator
vent outlet

3' (91 cm)

*

J

Clearance to non-
mechanical air
supply inletto
building or the
combustion air inlet
to any other
appliance

12" (30 cm)

9" (23 cm)

K

Clearance to
mechanical air sup-
ply inlet

6' (1.83 m)

3' (91 cm) above if within 10' (3 m)

horizontally

L

Clearance above
paved sidewalks or
paved driveway
located on private
property

7' (2.13 m)

+

7’ (2.13 m)

+

M

Clearance under
veranda, porch,
deck, or balcony

12' (30 cm)**

12" (30 cm)**