Appendix a, Ho-b data, Table a-1 beckett afg oil burner set-up – Royal Appliance Air Furnace User Manual
Page 18: Table a-2 riello 40f oil burner set-up
29733 R2 06/01/2003
18
TABLE A-1 BECKETT AFG OIL BURNER SET-UP
BECKETT AFG SERIES OIL BURNERS
FURNACE
MODEL
OUTPUT
BTU/Hr
BURNER
MODEL
NOZZLE
PUMP
PRESSURE
FLOW
RATE
HEAD
STATIC
PLATE
80F (060)
58,100
1, 2
AF76BO
0.50 / 70° W
100 PSIG
0.50 GPH
F0
3-3/8 in.
80F (070)
68,000
2
AF76BN
0.65 / 70° W
100 PSIG
0.65 GPH
F3
3-3/8 in.
80F (080)
78,900
2
AF76BN
0.70 / 70° W
100 PSIG
0.70 GPH
F3
3-3/8 in.
120F (090)
87,700
2
AF76BZHS
0.75 / 70° W
100 PSIG
0.75 GPH
F4
3-3/8 in.
120F (100)
98,800
AF76BZHS
0.85 / 70° W
100 PSIG
0.85 GPH
F4
3-3/8 in.
120F (120)
113,400
AF76BZHS
1.00 / 70° W
100 PSIG
1.00 GPH
F4
3-3/8 in.
1
F0 Head required for proper combustion.
2
Low Firing Rate Baffle required, Beckett Part No. 3708
In the United States, the R. W. Beckett “AFG” Burner may be equipped with Beckett’s “Inlet Air Shut-Off”, Beckett Part No. AF/A 5861, to increase efficiency. It
reduces the amount of air passing through the oil burner, combustion chamber, breeching, etc. up the chimney between burner cycles.
NOTE: THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP.
TABLE A-2 RIELLO 40F OIL BURNER SET-UP
RIELLO 40 F SERIES OIL BURNERS
FURNACE
MODEL
OUTPUT
BTU/Hr
BURNER
MODEL
NOZZLE
PUMP
PRESSURE
FLOW
RATE
HEAD
STATIC
PLATE
80F (060)
58,000
40 F3
0.40 / 60° W
160 PSIG
0.50 GPH
1.5
2.25
80F (070)
73,000
40 F3
0.50 / 60° W
150 PSIG
0.60 GPH
1.5
2.5
80F (080)
79,000
40 F3
0.60 / 60° W
145 PSIG
0.70 GPH
2.0
3.0
120F (090)
87,000
40 F3
0.75 / 70° W
150 PSIG
0.75 GPH
2.0
3.52
120F (100)
100,000
40 F3
0.85 / 70° W
150 PSIG
0.85 GPH
2.5
4.0
120F (120)
118,000
40 F3
1.00 / 70° W
160 PSIG
0.95 GPH
3.0
6.0
Appendix A
HO-B DATA