R7184 sequence of operation – Royal Appliance Air Furnace User Manual

Page 26

Advertising
background image

29733 R2 06/01/2003

26


IDLE STATE

THERMOSTAT CALLS FOR HEAT

SAFETY CHECK FOR FLAME

(5 SEC.)

BURNER MOTOR & IGNITOR START

SOLENOID VALVE OPENS

TRIAL FOR IGNITION

15 SEC.

BURNER FLAME MONITORED

CARRYOVER STATE

· Provides continuous spark

· LED diagnostic light ON

· Start Carryover Timer

CARRYOVER TIMER EXPIRES

RUN STATE

· Ignitor turns off.

THERMOSTAT SATISFIED

R7184 SHUTS OFF:

· Burner Motor

· Solenoid Valve

· LED Diagnostic Light

RETURNS TO IDLE STATE

FLAME

FLAME

FLAME

FLAME

NO FLAME

NO FLAME

FLAME LOST

FLAME LOST

REMAINS IN IDLE STATE

R7184

SEQUENCE of

OPERATION

LOCKOUT STATE

R7184:

· Shuts off burner motor

· Shuts off igniter

· Shuts off Solenoid Valve

· Fast Flashes LED Diagnostic

Light

TO EXIT LOCKOUT

PRESS RESET

RECYCLE TIMER STARTS

R7184:

· Shuts off Solenoid Valve

· Shuts off Ignitor

· Shuts off Burner Motor

· Slow Flashes LED

diagnostic light

RECYCLE TIMER EXPIRES

(60 SECONDS

FLAME LOST