3.7.2. IEEE 1613 Type Tests

IEEE Test

IEEE 1613 Clause

Description

Test Levels

Enclosure Contact

+/- 8kV

C37.90.3

9

ESD

Enclosure Air

+/- 12kV

C37.90.2

8

Radiated RFI

Enclosure ports

35 V/m

Signal ports

+/- 2kV

@ 2.5kHz

D.C. Power ports

+/- 2kV

C37.90.1

7

Fast Transient

Earth ground ports

+/- 2kV

Signal ports

2.2kV

common
mode @

1MHz

C37.90.1

7

Oscillatory

D.C. Power ports

2.2kV

common &

differential

mode @

1MHz

Signal ports

5 kV (Failsafe

Relay)

C37.90

6

H.V. Impulse

D.C. Power ports

5 kV

Signal ports

2kV

AC(Failsafe

Relay)

C37.90

6

Dielectric Strength

D.C. Power ports

1.2kV DC

Table 3.10. RS900GP IEEE 1613 Type Tests

• If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During

disturbance errors may occur but recovery is automatic).

• If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During

disturbance no errors will occur).

3.7.3. IEC Environmental Type Tests

Test

Description

Test Levels

Severity Levels

IEC 60068-2-1

Cold Temperature

Test Ad

-40°C, 16 Hours

N/A

IEC 60068-2-2

Dry Heat

Test Bd

+85°C, 16 Hours

N/A

IEC 60068-2-30

Humidity (Damp

Heat, Cyclic)

Test Db

95% (non-condensing),

55°C, 6 cycles

N/A

IEC 60255-21-1

Vibration

2g @ (10-150) Hz

Class 2

IEC 60255-21-2

Shock

30g @ 11 ms

Class 2

Table 3.11. IEC Environmental Type Tests