The total length of air supply pipe cannot exceed the

distances listed in Tables L and N. Each elbow used is

equal to 10 ft of straight pipe. This will allow installation

in any arrangement that does not exceed the lengths

shown in Tables L and N.

The vent cap is not considered in the overall length of

the venting system.

Care must be taken during assembly that all joints are

sealed properly and are airtight.

The vent must be installed to prevent the potential ac-

cumulation of condensate in the vent pipes. It is

required that:

1. The vent must be installed with a condensate

drain located in proximity to the heater as directed

by the vent manufacturer.

2. The vent must be installed with a slight upward

slope of not more than 1/4 inch per foot of hori-

zontal run to the vent terminal.

3. The vent must be insulated through the length of

the horizontal run.

Termination

The vent cap MUST be mounted on the exterior of the

building. The vent cap cannot be installed in a well or

below grade. The vent cap must be installed at least 1

ft above ground level and above normal snow levels.

The vent cap MUST NOT be installed with any com-

bustion air inlet directly above a vent cap. This vertical

spacing would allow the flue products from the vent

cap to be pulled into the combustion air intake installed

above.

This type of installation can cause non-warrantable

problems with components and poor operation of the

heater due to the recirculation of flue products. Multi-

ple vent caps installed in the same horizontal plane

must have a 4 ft clearance from the side of one vent

cap to the side of the adjacent vent cap(s).

Combustion air supplied from outdoors must be free of

particulate and chemical contaminants. To avoid a

blocked flue condition, keep the vent cap clear of

snow, ice, leaves, debris, etc.

The stainless steel flue direct vent cap must be fur-

nished by the heater manufacturer in accordance with

its listing (sales order option D-15).

Outdoor Installation

Outdoor models must be vented with listed vent mate-

rial per the following instructions and installed with the

optional factory-supplied outdoor vent kit. A special

vent cap and air intake hood are provided in accor-

dance with CSA requirements. These must be

installed directly on the vent pipe as illustrated in Fig.

29.

Care must be taken when locating the heater out-

doors, because the flue gases discharged from the

vent cap can condense as they leave the cap.

Improper location can result in damage to adjacent

structures or building finish. For maximum efficiency

and safety, the following precautions must be

observed:

1. Outdoor models must be installed outdoors and

must use the outdoor vent cap and air intake hood

available from the manufacturer (sales order

option D-11).

2. Periodically check venting system. The heater’s

venting areas must never be obstructed in any

way and minimum clearances must be observed

to prevent restriction of combustion and ventilation

air. Keep area clear and free of combustible and

flammable materials.

3. Do not locate adjacent to any window, door, walk-

way, or gravity air intake. The vent must be

located a minimum of 4 ft horizontally from such

areas.

4. Install above grade level and above normal snow

levels.

5. Vent terminal must be at least 3 ft above any

forced air inlet located within 10 ft.

6. Adjacent brick or masonry surfaces must be pro-

tected with a rust-resistant sheet metal plate.

WARNING: No substitutions of flue pipe or vent

cap material are allowed. Such substitutions would

jeopardize the safety and health of inhabitants.

NOTE: The vent cap and air intake hood must be

furnished by the heater manufacturer in accordance

with its listing (sales order option D-11).