MODULATING

*

Fig. 34: Mode 7 Primary/Secondary Piping with

External Target Temp

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Mode 8 – This mode is for remote firing control of the

heater via an external sequencer such as the Raypak

TempTracker MOD+. The Boil Max setting is the

heater shutdown temperature (max temperature). The

heater is enabled via dry contact at the Enable/Disable

connection at the low voltage terminal strip, and the fir-

ing rate is controlled by a 0-10 VDC signal from the

external sequencer. A control signal of ≥0.5 VDC

equates to minimum fire, and a signal of 10 VDC

equates to 100% firing rate. See Fig. 35.

NOTE: For Modes 7 and 8, connect to pins 13 and

14 on the low-voltage panel. See page 21. Use these

modes for systems using an external signal.

*