Roberts Gorden CRV-B-4 User Manual

Page 20

Advertising
background image

CRV-S

ERIES

D

ESIGN

M

ANUAL

14

5.2 Pump Capacity

The flow unit capacity of the pump is indicated on
Page 14, Table 2
, as a function of installed altitude.
When the CRV-Series system is designed in accor-
dance with this set of instructions and is in proper
operating condition, a vacuum from 2-3" w.c. will be
obtainable at each end vent (i.e. at all burners).

Table 2: Pump Capacity

There are a number of design requirements which, if
not met, will reduce the vacuum obtainable and
thereby the effective flow capacity of the pump. These
include:

Minimum Length of Tailpipe - If less than the

minimum length of tailpipe is provided per radiant
branch, there will be insufficient cooling of the com-
bustion gases and improper operation of the pump.

Line Loss Check for Tailpipe is applicable to

sections of tailpipe which are common to two or
more radiant branches (i.e. shared lengths). See
Page 14, Figure 15
.

Excessive back pressure on discharge line of

pump can be caused by partial blockage or too
much flow for length. See Section 5.3.1

More than maximum number of burners or flow

units per radiant branch. See Page 14, Table 2.

Excessive number of elbow or tee fittings

which increases vacuum loss.

5.3 Tailpipe Flow

Excessive flow loading in a single section of tailpipe
can cause low vacuum and lower effective pump
capacity. For the pump to develop the proper vacuum,
the length of tailpipe must not be excessive for the

number of flow units carried in the tube.

See Figure 15. Readings for length and flow when
plotted on the graph must fall on OK side to avoid
excessive vacuum losses.

FIGURE 15: Vacuum Loss Curve for 4" Shared
Tailpipe

NOTE: For 6" (15 m) tailpipe, length is limited to a
maximum of 100’ (30 m). See Page 16, Section 6.3
for more details.
Lengths shown include allowance for 1 elbow every
50' (15 m); deduct 15% of length for each additional
elbow used per 50' (15 m) length.

5.3.1 Pump Exhaust Length Requirements

The tube length on the exhaust side of the pump is
considered excessive if not within the following condi-
tions:

Table 3: Pump Exhaust Requirements

Installed Altitude

Maximum Flow Units

Feet Above

Sea Level

Meters Above

Sea Level

EP-100

EP-200

Series

EP-300

Series

0

'

- 2000

'

0 m - 609 m

66

112

224

2001

'

- 3000

'

610 m - 914 m

63

105

215

3001

'

- 4000

'

915 m - 1219 m

60

100

206

4001

'

- 5000

'

1220 m - 1524 m

57

95

197

5001

'

- 6000

'

1525 m - 1828 m

54

90

188

6001

'

- 7000

'

1829 m - 2134 m

51

84

180

7001

'

- 8000

'

2135 m - 2438 m

48

80

170

8001

'

- 9000

'

2439 m - 2743 m

45

75

161

Pump Series

Exhaust Tube Length Exhaust Tube Diameter

EP-100

Up to 25' (7.6 m)

4" 3 Elbows

EP-100

Up to 50' (15 m)

5" 3 Elbows

EP-200

Up to 10' (3 m)

4" 0 Elbows

EP-200

Up to 25' (7.6 m)

5" 3 Elbows

EP-200

Up to 50' (15 m)

6" 3 Elbows

EP-300

Up to 10' (3 m)

6" 1 Elbows

EP-300

Up to 25' (7.6 m)

7" 3 Elbows

EP-300

Up to 50' (15 m)

8" 3 Elbows

NOT OK

OK

SIDE

10

20

30

40

50

60

70

80

90

100

120

130

Length of

Tailpipe Section (f

eet)*

Maximum Flow Units per Single Tailpipe Section

30 40 50 60 70 80 90 100 110 120

Advertising
This manual is related to the following products: