SECTION 6: R

ADIANT

T

UBE

AND

T

AILPIPE

17

4. Select pump model series for total system flow

units:
EP-100: up to 66 flow units
EP-200: up to 110 flow units
EP-300: up to 224 flow units

5. See Page 14, Table 2 for altitudes greater than

2000'.

6. For each branch, add the length of radiant tube

after each heater:

Repeat this calculation for each branch in the
system.

7. Divide the total radiant tube length in the branch

by the number of burners in the branch to get
the average radiant length per burner.

Repeat this calculation for each branch in the
system.

8. Using the average radiant length per burner

(Calculated in Step 7) See Page 17, Table 4 to
select the allowable tailpipe lengths per flow
unit.

Table 4: Allowable Tailpipe Lengths

*Minimum tailpipe lengths can only be used if radiant tube length is recommended or greater.

Burner

Radiant Tube Length

After Each Burner

1

+

2

+

3

+

4

+

5

+

6

+

Total Radiant Tube
Length in Branch =

Average Radiant
Length Per Burner =

Burner Model

B-2

B-4

B-6

B-8

B-9

B-10

B-12/B-12A

Radiant Tube Length (average distance between burners)

Minimum (ft)

10

12.5

20

20

20

30

35

Recommended (ft)

15

20

25

30

30

40

50

Maximum (ft)

20

25

35

45

50

60

70

Tailpipe length per flow unit

Minimum (ft)*

1.2

1.2

1.2

1.2

1.2

1.2

1.2

Recommended (ft)

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Maximum (ft)

2.5

2.5

2.5

2.5

2.5

2.5

2.5

Maximum (ft) for EP-100 only

1.7

1.7

1.7

1.7

1.7

1.7

1.7