Table 8. technical data venting, Continued) – Reliance Water Heaters N71120NE User Manual
Page 19
19
model n100250ne/a
input: 250,000 btu/hr
total Vent height (feet)
Vent connector size: 6 inches
6
8
10
15
20
30
50
100
input btuh/hr rise
Vent connector diameter (inches)
250,000
1 ft
8
8
7
7
7
6
6
6
250,000
2 ft
7
7
7
7
6
6
6
6
250,000
3 ft
7
7
7
7
6
6
6
6
number
combined input
of heaters
in thousands of btu/hr
manifold and common Vent diameter (inches)
2
500,000
9
9
9
8
8
7
7
7
3
750,000
12
12
10
10
10
9
8
8
4
1,000,000
14
14
12
12
10
10
9
9
model n100275ne/a
input: 275,000 btu/hr
total Vent height (feet)
Vent connector size: 6 inches
6
8
10
15
20
30
50
100
input btu/hr
rise
Vent connector diameter (inches)
275,000
1 ft
8
8
7
7
6
6
6
6
275,000
2 ft.
8
8
7
7
6
6
6
6
275,000
3 ft
7
7
7
7
6
6
6
6
number of
combined input
heaters
in thousands of btu/hr
manifold and common Vent diameter (inches)
2
550,000
10
9
9
8
8
8
7
7
3
825,000
12
12
12
10
9
9
8
8
4
1,100,000
14
14
14
12
12
10
9
9
model n85310ne/a
input: 310,000 btu/hr
t otal Vent height (feet)
Vent connector size: 6 inches
6
8
10
15
20
30
50
100
input btu/hr
rise
Vent connector diameter (inches)
310,000
1 ft.
9
8
8
8
7
7
6
6
310,000
2 ft.
8
8
8
7
7
7
6
6
310,000
3 ft.
8
8
8
7
7
7
6
6
number of
combined input
heaters
in thousands of btu/hr
manifold & common Vent diameter
2
620,000
10
10
9
9
8
8
7
7
3
930,000
14
12
12
12
10
9
9
8
4
1,240,000
14
14
14
12
12
12
10
9
model n85366ne/a, n85390ne/a
input: 366,000, 390,000 btu/hr
total Vent height (feet)
Vent connector size: 6 inches
6
8
10
15
20
30
50
100
input btu/hr
rise
Vent connector diameter (inches)
366,000
1 ft
9
9
9
8
8
8
8
8
390,000
1 ft
10
9
9
9
8
8
8
8
366,000
2 ft
9
9
8
8
8
8
8
8
390,000
2 ft
9
9
9
8
8
8
8
8
366,000
3 ft
9
8
8
8
8
8
8
8
390,000
3 ft
9
9
8
8
8
8
8
8
number of
combined input
heaters
in thousands of btu/hr
manifold & common Vent diameter (inches)
2
732,000
12
10
10
9
9
9
8
8
780,000
12
12
10
10
9
9
8
8
3
1,098,000
14
14
14
12
12
10
9
9
1,170,000
14
14
14
12
12
10
10
9
4
1,464,000
16
16
14
14
14
12
12
10
1,560,000
16
16
16
14
14
12
12
10
table 8. technical data Venting
(continued)