model n100250ne/a

input: 250,000 btu/hr

total Vent height (feet)

Vent connector size: 6 inches

6

8

10

15

20

30

50

100

input btuh/hr rise

Vent connector diameter (inches)

250,000

1 ft

8

8

7

7

7

6

6

6

250,000

2 ft

7

7

7

7

6

6

6

6

250,000

3 ft

7

7

7

7

6

6

6

6

number

combined input

of heaters

in thousands of btu/hr

manifold and common Vent diameter (inches)

2

500,000

9

9

9

8

8

7

7

7

3

750,000

12

12

10

10

10

9

8

8

4

1,000,000

14

14

12

12

10

10

9

9

model n100275ne/a
input: 275,000 btu/hr

total Vent height (feet)

Vent connector size: 6 inches

6

8

10

15

20

30

50

100

input btu/hr

rise

Vent connector diameter (inches)

275,000

1 ft

8

8

7

7

6

6

6

6

275,000

2 ft.

8

8

7

7

6

6

6

6

275,000

3 ft

7

7

7

7

6

6

6

6

number of

combined input

heaters

in thousands of btu/hr

manifold and common Vent diameter (inches)

2

550,000

10

9

9

8

8

8

7

7

3

825,000

12

12

12

10

9

9

8

8

4

1,100,000

14

14

14

12

12

10

9

9

model n85310ne/a
input: 310,000 btu/hr

t otal Vent height (feet)

Vent connector size: 6 inches

6

8

10

15

20

30

50

100

input btu/hr

rise

Vent connector diameter (inches)

310,000

1 ft.

9

8

8

8

7

7

6

6

310,000

2 ft.

8

8

8

7

7

7

6

6

310,000

3 ft.

8

8

8

7

7

7

6

6

number of

combined input

heaters

in thousands of btu/hr

manifold & common Vent diameter

2

620,000

10

10

9

9

8

8

7

7

3

930,000

14

12

12

12

10

9

9

8

4

1,240,000

14

14

14

12

12

12

10

9

model n85366ne/a, n85390ne/a

input: 366,000, 390,000 btu/hr

total Vent height (feet)

Vent connector size: 6 inches

6

8

10

15

20

30

50

100

input btu/hr

rise

Vent connector diameter (inches)

366,000

1 ft

9

9

9

8

8

8

8

8

390,000

1 ft

10

9

9

9

8

8

8

8

366,000

2 ft

9

9

8

8

8

8

8

8

390,000

2 ft

9

9

9

8

8

8

8

8

366,000

3 ft

9

8

8

8

8

8

8

8

390,000

3 ft

9

9

8

8

8

8

8

8

number of

combined input

heaters

in thousands of btu/hr

manifold & common Vent diameter (inches)

2

732,000

12

10

10

9

9

9

8

8

780,000

12

12

10

10

9

9

8

8

3

1,098,000

14

14

14

12

12

10

9

9

1,170,000

14

14

14

12

12

10

10

9

4

1,464,000

16

16

14

14

14

12

12

10

1,560,000

16

16

16

14

14

12

12

10

table 8. technical data Venting