checking Venting

The following steps shall be followed with each appliance

connected to the venting system placed in operation, while any

other appliances connected to the venting system are not in

operation.

1. Seal any unused openings in the venting system.

2. Inspect the venting system for proper size and horizontal pitch,

as required in the National fuel gas Code, ANSI Z223.1or the

CAN/CgA B149 Installation Codes and these instructions.

Determine that there is no blockage or restriction, leakage,

corrosion and other deficiencies which could cause an unsafe

condition.

3. So far as is practical, close all building doors and windows

and all doors between the space in which the water heater(s)

connected to the venting system are located and other spaces

of the building. Turn on all appliances not connected to the

venting system. Turn on all exhaust fans, such as range hoods

and bathroom exhausts, so they shall operate at maximum

speed. Close fireplace dampers.

4. follow the lighting instruction. Place the water heater being

inspected in operation. Adjust thermostat so appliance shall

operate continuously.

5. Test for spillage at the burner level after 5 minutes of main

burner operation.

6. After it has been determined that each appliance connected

to the venting system properly vents when tested as outlined

above, return doors, windows, exhaust fans, fireplace

dampers and any other gas burning appliance to their previous

conditions of use.

7. If improper venting is observed during any of the above tests,

the venting system must be corrected.

fAILure To CorreCT BACK DrAfTS mAY CAuSe AIr

CoNTAmINATIoN AND uNSAfe CoNDITIoNS.

• If the back draft cannot be corrected by the normal method or

if a suitable draft cannot be obtained, a blower type flue gas

exhauster must be employed to assure proper venting and

correct combustion.

check the igniter assembly

At least once a year, check the igniter assembly, figure 23, and

the main burner, figure 24, for proper operation. refer to the
following igniter assembly and main burner sections.

igniter assembly

for access to igniter assembly, unfasten two screws to burner

cover and remove. Locate the burner with the igniter assembly

and remove screw holding burner to manifold. Slide burner out

to access igniter assembly.

Servicing of the igniter assembly includes keeping the igniter free

of lint, scale or any other foreign debris.

figure 23. igniter

main burner

The main burner, figure 24, should display the following

characteristics:

• Cause rapid ignition and carry across entire burner.

• give reasonably quiet operation during ignition, burning, and

extinction.

• Cause no excessive lifting of flame from burner ports.

figure 24.

If the preceding burner characteristics are not evident, check for

accumulation of lint, scale or other foreign debris that restricts or

blocks the air openings to the burner or heater.
NoTe:
1. remove main burners from unit.
2. Check that burner venturi and ports are free of foreign debris.
3. Clean burners with bristle brush and/or vacuum cleaner - Do

NoT distort burner ports or pilot location.

4. reinstall burners in unit. make sure front and rear of burners

are installed correctly in burner support brackets.

Also check for good flow of combustion and ventilating air to the

unit. maintain a clear area around the heater at all times.

gas ValVes

figure 25 shows the type of combination manual gas control valve

and regulator used on these heaters.
If the gas valve becomes defective, repairs should not be

attempted. A new valve should be installed in place of the

defective one.

figure 25.