The FMG-3001 and FMG-3101 Magmeters output an open collector frequency signal.

A 10 KΩ pull up resistor must be connected between terminals 1 and 2 if the magmeter is used with third-party equipment..

8. Wiring the FMG-3001 and FMG-3101 with Frequency output

1

2

3

4

5 to 24 VDC

Ground

Not used

Frequency Out

Magmeter

10K

W

Install a pull-up resistor when connecting the
Magmeter to other manufacturer's flowmeters.

1

2

3

4

5 to 24 VDC

Ground

Not used

9

8

7

Sensr Gnd
(SHIELD)

Sensr IN
(RED)

Sensr V+
(BLACK)

Magmeter FP90

Flow

Transmitter

Frequency

3

4

Frequency

Connect AUX power on
the FP90 to provide the
power to the FMG3000
OPEN COLLECTOR
output.

Blue Jumper
ON

Metal Installation Fittings

Iron Saddles

PIPE SIZE FITTING

K-Factor

K-Factor 20 mA=

20 mA=

(IN.)

TYPE

Gallons

Liters*

in GPM

in LPM

SCH 80 IRON SADDLE ON SCH 80 PIPE
2 FP-5320GIS

194.85

51.48

153.96

582.75

2½ FP-5325GI

142.28

37.59

210.86

798.10

3 FP-5330GI

87.53

23.13

342.72

1297.20

4 FP-5340GI

40.62

10.73

738.58

2795.54

5 FP-5350GI

29.28

7.74

1024.43

3877.48

6 FP-5360GI

22.30

5.89

1345.58

5093.03

8 FP-5380GI

12.52

3.31

2395.41

9066.64

10 FP-5381GI

7.94 2.10

3778.75

14302.5

12 FP-5382GI

5.65

1.49

5311.45

20103.8

SCH 80 IRON SADDLE ON SCH 40 PIPE
2 FP-5320GIS

185.35

48.97

161.85

612.61

2½ FP-5325GI

127.47

33.68

235.36

890.83

3 FP-5330GI

76.62

20.24

391.54

1481.99

4 FP-5340GI

40.23

10.63

745.72

2822.57

5 FP-5350GI

27.32

7.22

1098.24

4156.83

6 FP-5360GI

19.71

5.21

1521.92

5760.46

8 FP-5380GI

11.61

3.07

2584.23

9781.30

10 FP-5381GI

7.36

1.94

4078.8

15438.2

12 FP-5382GI

5.18

1.37

5793.39

21927.9

9. Calibration Data: K-Factors* and Full Scale Current Values