2.4 I/O Register Address


The OME-A-8111 occupies 16 consecutive PC I/O addresses. The following
table lists the registers and their locations.

Address Read

Write

Base+0

8254 Counter 0

8254 Counter 0

Base+1

8254 Counter 1

8254 Counter 1

Base+2

8254 Counter 2

8254 Counter 2

Base+3

Reserved

8254 Counter Control

Base+4

A/D Low Byte

D/A Channel 0 Low Byte

Base+5

A/D High Byte

D/A Channel 0 High Byte

Base+6

DI Low Byte

Reserved

Base+7

DI High Byte

Reserved

Base+8

Reserved

A/D Clear Interrupt Request

Base+9

Reserved

A/D Gain Control

Base+A

Reserved

A/D Multiplexer Control

Base+B

Reserved

A/D Mode Control

Base+C

Reserved

A/D Software Trigger Control

Base+D

Reserved

DO Low Byte

Base+E

Reserved

DO High Byte

Base+F Reserved

Reserved