Installation - electronic (relay output only) – Omega Engineering FPR 200 User Manual

Page 8

Advertising
background image

Installation - Electronic (Relay Output Only)

1. Connect the red wire from the sensor to the positive terminal of the

12-35 V

DC

power supply.

2. Connect the black wire from the transmitter to the negative terminal

of the 12-35 V

DC

power supply.

3. (Versions with stainless steel sensor body only) Be sure to properly

ground the flow sensor by using the ground screw shown

in Illustration 2 to

connect the sensor body

Earth ground. This step

may be unnecessary if

the piping system that the

flow sensor is plumbed

into is already connected

to Earth ground.

4. Wire the appropriate relay contacts to the load that is to be

switched per Table 1 below.

5. If the unit is operating correctly, the green power indication LED

and the red relay status LED should illuminate after the DC supply

voltage is turned on. As fluid flow is increased above the factory-

adjusted set point, the red relay status LED should turn off.

If the LEDs do not illuminate when power is applied:

„ check wiring terminations for good connections

„ verify that the DC supply voltage is between 12 and 35 V

DC

Table 1.: Wiring Connections

(8)

Wire Color

Connection

Red

+12-35 V

DC

Black

DC Ground

Green

Relay Common

White

Relay Normally Closed Contact

Brown

Relay Normally Open Contact

Illustration 2

GROUND SCREW