8254 counter, A/d input buffer register, 2 a/d input buffer register – Omega ISA- BUS MULTI-FUNCTIONAL BOARD OME-A822PG User Manual

Page 19

Advertising
background image

2.4.1 8254 Counter


The 8254 Programmable timer/counter has 4 registers from Base+0 through
Base+3. For detailed programming information on the 8254 , please refer to
Intel‘s “Microsystem Components Handbook”.

Address

Read

Write

Base+0

8254 Counter 0

8254 Counter 0

Base+1

8254 Counter 1

8254 Counter 1

Base+2

8254 Counter 2

8254 Counter 2

Base+3

Reserved

8254 Counter Control




2.4.2 A/D Input Buffer Register


(READ) Base+4 : A/D Low Byte Data Format
Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

D7 D6 D5 D4 D3 D2 D1 D0

(READ) Base+5 : A/D High Byte Data Format
Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0 0 0 READY

D11

D10

D9

D8


A/D 12 bit data : D11…..D0, D11=MSB, D0=LSB
READY =1 : A/D 12 bit data not ready

=0 : A/D 12 bit data is ready


The low 8 bit A/D data is stored in address BASE+4 and the high 4 bit data is stored in
address BASE+5. The READY bit is used as an indicator for the A/D conversion. When an
A/D conversion is completed, the READY bit will clear to zero.