I/o specifications input specifications, High-speed counter inputs – Omron E7 User Manual

Page 4

Advertising
background image

368

3G3RV-P10ST

@

-E

Note: 1.

The DM area, HR area, AR area, and counter values are
backed up. If the backup battery or capacitor is discharged,
the contents of these areas will be lost and the data values will
revert to the defaults.

2.

The contents of the program area, read-only DM area
(DM6144 to DM6599), and PLC setup (DM 6600 to DM 6655)
are stored in flash memory. The contents of these areas will
be read from flash memory the next time the power is turned
ON, even if the backup battery or capacitor is discharged.
When data has been changed in any of these areas, write the
new values to flash memory by switching the 3G3RV-P10ST
to MONITOR or RUN mode, or by turning the power OFF and
then ON again.

3.

Changes made while in MONITOR mode using, for example,
online editing, are written to flash memory in real-time.

4.

The above figure for power consumption includes the power
consumption of the programming console.

5.

This input is shared by the high-speed counter and synchro-
nized pulse control functions.

6.

This output is shared by the pulse output and synchronized
pulse control functions.

I/O specifications

Input specifications

Note:

The input time constant can be set to 1, 2, 3, 5, 10, 20, 40, or 80 ms in the PLC setup.

High-speed counter inputs

The following unit input bits can be used as high-speed counter inputs. The maximum count frequency is 5 kHz in differential phase mode and
20 kHz in the other modes.

Power-interruption hold function

Holds the contents of HR, AR, CNT, and DM areas.

Memory backup (see notes 1 and 2.)

Flash memory:

Program, read-only DM area, and PC setup

Memory backup: The read/write DM area, HR area, AR area, and counter values are backed up.

(The battery has a 5-year lifetime at 25 °C and it is replaceable.)

Self-diagnostic function

CPU errors, memory errors, communications errors, setting errors, battery errors

Program check

No END instruction, program errors (regularly checked during operation)

Connected tools

CX-programmer

After version 2.1

Programming console

C200H-PRO27, CQM1-PRO01

SSS

PC98 & PC/AT (SYSMAC support software, all versions)

CX-drive

Version 1 or higher

Item

Specifications

3G3RV-P10ST8-E

3G3RV-P10ST8-DRT-E

Item

Inputs

Specification

Input voltage

All

24 VDC

+10%

/

-15%

Input impedance

IN 00000 to IN 00001

2.7 k

Ω

IN 00002 to IN 00004

3.9 k

Ω

IN 00005

4.7 k

Ω

Input current

IN 00000 to IN 00001

8 mA typical

IN 00002 to IN 00004

6 mA typical

IN 00005

5 mA typical

ON voltage/current

IN 00000 to IN 00001

17 VDC min., 5 mA

IN 00002 to IN 00005

14.4 VDC min., 3.5 mA

OFF voltage/current

All

5.0 VDC max., 1.1 mA

ON delay

All

1 to 80 ms max. Default: 10 ms (see note.)

OFF delay

All

1 to 80 ms max. Default: 10 ms (see note.)

Circuit configuration

IN 00000 to IN 00001

IN 00002 to IN 00004

IN 00005

IN

COM

1k

Ω

0.01
µF

Input LED

Internal circuits

2.7 k

Ω

IN

COM

820

Ω

Input LED

Internal circuits

3.9 k

Ω

IN

COM

750

Ω

Input LED

Internal circuits

4.7 k

Ω

Input

Function

Differential phase mode

Pulse plus direction input mode

Up/down input mode

Increment mode

IN 00000

A-phase pulse input

Pulse input

Increment pulse input

Increment pulse input

IN 00001

B-phase pulse input

Direction input

Decrement pulse input

Normal input

IN 00002

Z-phase pulse input or hardware reset input (IN00002 can be used as a normal input when it is not used as a high-speed counter input.)

Y203-EN2-02-Katalog.book Seite 368 Mittwoch, 24. Mai 2006 2:22 14

Advertising