Omron E7 User Manual

Page 7

Advertising
background image

G7/F7/L7/E7 inverter PLC

371

6.

Communications port

Connects the PLC to a programming device (including programming
consoles), host computer, or standard external device. Use a proper
connecting cable (CPM2C-CN111, CS1W-CN114, CS1W-CN118, or
CS1W-CN226).

Note: 1.

A CQM1H-PRO01-E programming console can be connect-
ed directly to the PLC.

2.

A C200H-PRO27-E programming console can be connected
directly to the PLC with a CS1W-CN224/CN624 connecting
cable.

3.

Use a CPM2C-CN111 or CS1W-CN114 connecting cable to
connect to the communications port as a peripheral port. The
communications port can be used simultaneously as both a
peripheral port and RS-232C port by using the CPM2C-
CN111 connecting cable.

4.

Use a CPM2C-CN111, CS1W-CN118 or CS1W-CN226 con-
necting cable to connect to the communications port as a RS-
232C port. The communications port can be used simulta-
neously as both a peripheral port and RS-232C port by using
the CPM2C-CN111 connecting cable

Note:

The peripheral port and RS-422/485 port cannot be used simul-
taneously. When using the peripheral port disconnect any
devices connected to the RS-422/485 port.

7.

Communications switch

Switch to select port 1 type of connected device

8.

DeviceNet port (-DRT versions only)

Terminal arrangement

9.

RS-422/485 port

Used to connect to host computers, or standard external devices.
Terminal arrangement

Note:

The maximum line length is 500 m.
The peripheral port and RS-422/485 port cannot be used simul-
taneously. When using the peripheral port disconnect any
devices connected to the RS-422/485 port.
When using RS-485 communication, connect RDA- to SDA- and
RDB+ to SDB+.

10. Terminating resistance switch

Set this switch to ON only for double-ended connection to a host link
network.

11. CompoBus/S port

Terminal arrangement

Use special flat cable or VCTF cable for the transmission lines that con-
nect the nodes in the CompoBus/S I/O Link. (Special flat cables and
VCTF cables cannot be combined in the same system.)

12. Digital inputs and outputs and encoder interface

Connects the CPU unit to external input and output devices.
Sourcing outputs

13. Functional earth-wire

To be connected the earth connection inside the inverter.

14. Battery

15. Low battery detection switch

This switch enables or disables the detection of a low-battery error.

16. DeviceNet node-number (-DRT versions only)

Please refer to the DeviceNet section

17. DeviceNet indicators (-DRT versions only)

Please refer to the DeviceNet section

18. CompoBus/S indicators

Position

Communication port 1

OFF (up) (default)

Programming console

ON (down)

RS-422/485 communication

Position

Termination

OFF (right)
(default)

Disabled

ON (left)

Enabled

CAN-H

CAN-L

V+

V-

Shield

SDA-

RDB+

RDA-

SDB+

6

5

Send

data

(output)

Receive

data

(input)

ON

1

Name

Model number

Specifications

Flat cable

XB1T-W10

4-core flat cable, 0.75 mm²

VCTF cable

---

2-core VCTF, 0.75 x 20

Position

Low-battery detection

OFF (right)
(default)

Error detection enabled

ON (left)

Error detection disabled

Indicator

Status

Meaning

SD
(yellow)

Flashing

Data is being transmitted via
CompoBus/S

OFF

Data isn't being transmitted via
CompoBus/S

RD
(yellow)

Flashing

Data is being received via
CompoBus/S

OFF

Data isn't being received via
CompoBus/S

ERC
(red)

Flashing

A CompoBus/S communications
error occurred.

OFF

A CompoBus/S communications
error hasn't occurred.

3

2

1

4

BDH

BDL

IN2(Z)

IN1(B)

IN0(A)

IN3

COM

IN5

IN4

OUT2

OUT1

OUT0

OUT3

A+

A-

Z+

B-

B+

Z-

COM(+)

ON

1

SD

RD

ERC

Y203-EN2-02-Katalog.book Seite 371 Mittwoch, 24. Mai 2006 2:22 14