CPSMP-200

8

Tech Support: 1-800-260-1312 -- International: 00-1-952-941-7600 -- (24 hours)

Replace the Fuse

CAUTION: Ensure that the power supply module has been disconnected
from the external power source and the module’s On/Off switch has been
set to “0”. Failure to observe this caution could result in damage to, and
subsequent failure of, the power supply module.

NOTE: The CPSMP-200 power supply module may be “hot swapped” (i.e.,
serviced while the chassis is in operation) provided the module to be serviced
has been disconnected from its external power supply and the module’s
On/Off switch has been set to “0”.

To replace the fuse in the CPSMP-200 power supply module:

1.

Ensure the On/Off switch on the power supply module is set to “0”.

2.

Disconnect the AC power cord from the external power source.

3. From the inside edge of the power receptacle, insert a small flat blade

screwdriver into the groove on the front, inside edge of the fuse holder
and carefully pry the fuse holder from the power supply module.

4.

Carefully remove the fuse from the fuse holder.

5.

Install a same size and rating replacement fuse in the fuse holder.

6.

Return the fuse holder and fuse to the installation position in the power
supply module. Snap the fuse holder into place.

7.

See the “Connect to External Power” section (page 5) for instructions on
re-connecting the power supply module to the external power source.

I
0

On/Off Switch

Fuse Holder

Fuse

[email protected] -- Click the “Transition Now” link for a live Web chat.

9

Technical Specification

For use with Transition Networks Model CPSMP-200 or equivalent.

Standards

UL Listed EN60950; FCC & CISPR Class A&B;
EN61000-3-2 Class D; CE Mark

Dimensions

8.3" x 8.4" x 2.7" (211 mm x 211 mm x 69 mm)

Weight

1 lb. (0.45 kg) approximately

Power Input

100-240 V, 47/63Hz, 0.62-1.5 Amp,
(typical with a fully-loaded chassis)

Voltage Tolerance

± 10%

Low-Line Input Current 3.3A max.

Inrush Current

40A max.( peak starting current) @ high line

Transient Recovery Time 1ms max.

Power Output

12VDC at 10.83 Amp max.

Power Factor

> 0.95 (no inductive or capacitive distinction)

Fuse

4 Amp/250 V

MTBF

60,000 hours (MIL217F2 V5.0) (MIL-HDBK-217F)
248,000 hours (Bellcore7 V5.0)

Environment

Tmra*:

0 to 60°C (32 to 140°F )

Storage Temperature:

-20 to 85°C (-4 to 185°F)

Humidity:

5 to 95%, non condensing

Altitude:

0 to 10,000 feet

Warranty

Lifetime

*Manufacturer’s rated ambient temperature: Tmra range for this power supply
module depends on the physical characteristics and the installation configuration
of the Transition Networks PointSystem™ chassis in which this module will be
installed.