Teledyne Field Wizard 2101 User Manual

Page 38

Advertising
background image

2101 Field Wizard
Section 3 Operation

3-14

2100 Series Site Setup – If you press F2 NEXT and advance to
a 2100 Series module, the Setup display shown in Figure 3-13
will appear.

Figure 3-13 Site Setup Display

The Site Setup display is used to calibrate sensors and run diag-
nostics on sensors. Module sensor information, such as level and
flow rate, is presented inside the display window. Use the Up and
Down arrow keys to scroll within the window.

Measurement Calibration – Level sensors can be calibrated
using the Field Wizard. Before you can calibrate, one valid
reading must have been taken so there is a value to calibrate to.

On the Site Setup display, use F2 NEXT to display the module
you want to calibrate, then press F3 CALIB. The Level Cali-
bration window for the selected module will appear (Figure 3-14).

Figure 3-14 Level Calibration Display

The level currently being detected will be displayed. To change
the level, use the numeric keys and then press Enter. You will be
returned to the Site Setup display. The message “Updating” will
appear in the Level field momentarily while the system updates
its information.

To clear an entry, press F4 CLEAR. To cancel the process and
return to the Site Setup display, press F6 CANCEL.