SDT 2004 is a powerful temperature differential control unit. It has *two programs and
may be used in a wide range of applications:


PROGRAM 0 – This program is USDT 2004's basic program. Set at the factory, it uses two
sensors to control a simple solar water heating system.

PROGRAM 1- This program allows the user to customize USDT 2004 for applications where a
third sensor is required. With this program you may, for example, measure the flow rate or the
temperature of the storage tank (T

3

, top of the tank).


*

USDT 2004 has additional programs available for a wide variety of advanced applications, these programs are not

supported at this time.


The control unit has the following functions
:

2 inputs for temperature sensors (PROGRAM 0)

1 input for flow rate measurement or additional temperature sensor (PROGRAM 1)

BTU meter capability for constant flow rate or with a flow meter

Adjustable hysteresises dependant on temperature

Adjustable (-3

o

F to 41

o

F) frost protection

Adjustable (200

o

F to 299

o

F) overheating protection

Adjustable (4.1

o

F to 99

o

F) temperature difference ?T

Manual override of pump for system testing

Digital display of all parameters

System status and diagnostic displays

Program 0 – Two Sensor Operation (Factory Setting)

Program 0 monitors the collector temperature (T

1

, at S

1

) and the return temperature (T

2

, at S

2

,

bottom of the storage tank). The solar loop circulation pump runs while the collector temperature
exceeds the return temperature by an adjustable
temperature difference diff. To avoid overheating, the
circulation pump stops if the return temperature (T

2

)

reaches the adjustable high limit (T

MAX

) temperature. The

temperature hysteresis (a lagging in the set -point) may
over-ride diff to avoid pump cycling.

The pump A1 runs only when the temperature at the
collector sensor location S1 is higher than the return
temperature at location S2 by at least diff (?T). The pump
stops if diff is less than the preset value or, when the
temperature at location S2 has reached the T

MAX

:

A1 (ON) only when S1 > (S2 + diff) & S2 < T max

U

S1

S2

A1