Thermo Products USDT2004 User Manual

Page 8

Advertising
background image

8

RUV X.X – This display shows the software revision number.
NR O – This is PROGRAM 0 which indicates simple operation of unit as a Universal Solar
Differential Temperature (USDT) controller. Change this value to 1 (NR 1) for activation of the
third sensor or pulse flow meter input (PROGRAM 1).

Hysteresis Bandwidth

User can program hysteresis (temperature range for output control) by using max

? and max=.

For

max

?1

Pump stops above tank temperature (T2)

max

=1

Pump runs again below this set point (T2)


Delta T Adjustment

diff

=1

Pump runs when temperature difference between collector T1 (collector) and T2
(tank) exceeds this value. Factory setting is 15

o

F. Consult your collector

manufacturer for the recommended value.


diff

?1

Pump stops when temperature difference between collector T1 (collector) and T2
(tank) reaches this value. Factory setting is 7

o

F. Consult your collector

manufacturer for the recommended value.

Manual Operation Mode

AUTO

The above display indicates that the unit is working in automatic mode. The
pump starts at a temperature difference of 15

o

F and runs as long as ? T is

above 7

o

F. The

B symbol appears in upper display line next to the collector