Application considerations – Trane Fan User Manual

Page 15

Advertising
background image

15

The following is the procedure to use
when selecting a fan for elevations and
temperatures other than standard:
1
Determine the air density from
Figure A-3.
2
Divide static pressure at the non-
standard condition by the air density
ratio.
3
Use the actual cfm and corrected static
pressure to determine rpm and bhp
from the fan performance tables.
4
The rpm is correct as selected.
5
The bhp must be multiplied by the air
density ratio determined in step one to
get the actual operating bhp.

Option and Installation Kt Corrections
System effect losses due to less than
ideal inlet or outlet configuration can be
expressed in terms of velocity pressure
by the following expression:

Inlet SP Loss =

Kti

(

Inlet Velocity

)

2

4005

Where Kti =
Inlet Option Kt + Inlet Installation Kt
Outlet SP Loss =

Kto

(

Outlet Velocity

)

2

4005

Where Kto = Outlet Option Kt + Outlet
Installation Kt

Kt is the loss factor for the inlet or
discharge condition being considered.

It is necessary to add all of the static
pressure loss determined from the
above equation to the component
static pressure to determine the point
of duty static pressure for selection of
the fan.

Fan Option Kt Corrections
The fan static pressure should be
adjusted for fan options. Option
pressure drops are documented as Kt
losses and are handled the same way
as installation Kt effects (losses). Use
Table A-1, Q Fan/Super Q II Fan Kt
corrections, to determine the Kt values.
Add these values to any installation Kt
values. Use the result to select the fan.

Table A-2 — Q Fan/Super Q II Fan Option Kt Corrections

Super Q II

Pressure

Options

Use

Q-Fan

Fan

Drop (Kt)

Inlet Flange

Connects to bolted inlet duct

X

0

Inlet Bellmouth*

Reduces Unducted Inlet Kt

X

X

-.1

Inlet Plus Silencer

Reduces inlet noise

X

X

+.1

Inlet Screen

Protects Unducted Inlets

X

X

+.1

Outlet Screen

Protects Unducted Outlets

X

+.5

Outlet Flange

Connects to bolted outlet duct

X

0

Outlet Equalizer (Diffuser)

Improves SE

X

0

Outlet Plus Silencer

Reduces Outlet Noise

X

X

+.1

Outlet Flow Stabilization Screen

Reduces Outlet swirl

X

X

+.8

Outlet Backdraft Damper

Isolates fan from duct

Special

Special

+.5

Frequency Drive Modulation

Modulates Q Fan quietly

Special

Special

0

Belt Guard

Protects drives/belts

X

0

Motor Rails

Allows motor to be mounted

X

Included

0

Standard Isolators

Isolates fan

X

Included

0

Seismic Isolators

Isolates fan

X

Special

0

*Note: Bellmouth effect included in unducted installation Kt correction. Fan sizes 49 through 60 fan curves are cataloged
with inlet bells. For unducted inlets without bells on size 49 through 60 fans add .1 to the inlet Kt given above.

Inlet vane losses are covered in the Selection Procedure with air density corrections (page 20).

Application
Considerations

Table A-1 — Q Fan/Super Q II Fan Installation Kt Corrections

Unducted (Plenum) Inlet*
Draw-Thru Type Design

0.0

Ducted Inlet
Turn > 3 Dia Upstream

-1.0

Turn

2 Dia Upstream

+.8

Turn

1 Dia Upstream

+1.3

Turn < 1 Dia Upstream

Not Recommended

Unducted Outlet
Blow-Thru Type Design

+.8

Ducted Outlet
Turn > 2 Dia Downstream

0.0

Turn

1 Dia Downstream

+1.3

Turn < 1 Dia Downstream

Not Recommended

Figure A-4 — Ducted Turns Near Q Fan