Pressure Class Limits

Class

Maximum RPM

I

857

II

1151

Fan Size 54”

Wheel Dia.

54.3 inches

1378 mm

Inlet Area

18.37 square feet

1.707 m

2

Outlet Area

18.37 square feet

1.707 m

2

Tip Speed

14.20 x RPM

4.328

ft./minute

m/minute

Minimum Fan RPM (Without VFRB Option)

Motor

Minimum Fan RPM

1800 RPM

292

1200 RPM

195

Performance
Data

Q Fan
Size 54

Table P-12 — Size 54 Q-Fan

CFM

Out-

Total Static Pressure

Std.

let

1

/

4

3

/

8

1

/

2

5

/

8

3

/

4

1”

1

1

/

4

1

1

/

2

1

3

/

4

2”

Air

Vel.

RPM

BHP

RPM BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP RPM

BHP

16200 881

323

1.2

344

1.6

365

1.9

387

2.4

410

2.8

17600 958

344

1.4

363

1.8

382

2.2

402

2.6

422

3.1

19000 1034

365

1.7

383

2.1

401

2.5

419

2.9

437

3.4

475

4.4

20400 1110

387

1.9

403

2.3

420

2.8

437

3.2

454

3.7

488

4.8

21800 1186

410

2.2

425

2.7

440

3.1

456

3.6

471

4.1

503

5.2

536

6.3

23200 1262

432

2.6

446

3.0

460

3.5

475

4.0

490

4.5

519

5.6

550

6.8

582

8.1

24600 1339

455

3.0

468

3.4

481

3.9

495

4.5

509

5.0

537

6.1

565

7.3

594

8.6

625

10.0

26000 1415

479

3.4

491

3.9

503

4.4

516

4.9

529

5.5

555

6.6

581

7.8

608

9.2

636

10.6

666

12.1

27400 1491

502

3.8

513

4.3

525

4.9

537

5.4

549

6.0

574

7.2

599

8.4

624

9.8

650

11.2

677

12.7

28800 1567

525

4.3

536

4.9

547

5.4

558

6.0

570

6.6

594

7.9

617

9.1

641

10.5

665

11.9

690

13.5

30200 1643

549

4.9

559

5.5

569

6.0

580

6.6

591

7.2

613

8.6

636

9.9

658

11.2

681

12.7

705

14.2

31600 1720

572

5.5

582

6.1

592

67

602

7.3

612

7.9

633

9.3

655

10.7

676

12.0

698

13.5

720

15.0

33000 1796

596

6.2

605

6.8

615

7.4

624

8.0

634

8.7

654

10.0

675

11.5

696

12.9

716

14.4

737

15.9

34400 1872

620

6.9

629

7.5

638

8.1

647

8.8

656

9.5

675

10.9

695

12.4

715

13.9

734

15.3

754

16.9

35800 1948

644

7.7

652

8.3

661

8.9

669

9.6

678

10.3

696

11.8

715

13.3

734

14.9

753

16.4

772

17.9

37200 2025

668

8.5

676

9.1

684

9.8

692

10.5

701

11.2

718

12.7

736

14.2

754

15.9

773

17.5

791

19.2

38600 2101

691

9.4

699 10.1

707

10.8

715

11.5

723

12.2

740

13.7

757

15.3

775

17.0

792

18.7

810

20.4

40000 2177

715

10.3

723 11.0

731

11.7

738

12.5

746

13.2

762

14.8

778

16.4

795

18.1

812

19.9

829

21.6

41400 2253

739

11.4

747 12.1

754

12.8

761

13.6

769

14.3

784

15.9

800

17.6

816

19.3

833

21.1

849

22.9

42800 2329

763

12.4

770 13.2

778

13.9

785

14.7

792

15.5

807

17.1

822

18.8

837

20.6

853

22.4

869

24.3

44200 2406

788

13.6

794 14.4

801

15.1

808

15.9

815

16.8

829

18.4

844

20.2

858

21.9

873

23.8

889

25.7

45600 2482

812

14.8

818 15.6

825

16.4

831

17.2

838

18.1

852

19.8

866

21.5

880

23.4

894

25.3

909

27.2

47000 2558

836

16.1

842 17.0

849

17.8

855

18.6

862

19.5

875

21.2

888

23.0

902

24.9

916

26.8

930

28.8

48400 2634

860

17.5

866 18.4

872

19.2

879

20.1

885

20.9

898

22.7

911

24.6

924

26.5

937

28.4

951

30.4

CFM

Out-

Total Static Pressure

Std.

let

2

1

/

4

2

1

/

2

3”

3

1

/

2

4”

4

1

/

2

5”

5

1

/

2

6”

6

1

/

2

Air

Vel.

RPM

BHP

RPM BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP RPM

BHP

29000 1578

717

15.2

744 16.9

30400 1654

730

16.0

755 17.7

31800 1731

745

16.8

767 18.5

815

22.2

33200 1807

760

17.7

782 19.5

826

23.1

34600 1883

777

18.7

797 20.5

838

24.2

882

28.2

36000 1959

794

19.8

813 21.6

852

25.3

893

29.3

37400 2035

811

20.9

830 22.7

867

26.5

906

30.5

946

34.8

38800 2112

830

22.2

847 23.9

883

27.7

920

31.8

957

36.1

997

40.6

40200 2188

849

23.6

865 25.2

900

29.0

935

33.2

970

37.5

1007

42.0

41600 2264

868

25.0

884 26.8

917

30.5

950

34.6

985

39.0

1019

43.5

1056

48.3

43000 2340

888

26.4

903 28.3

935

32.0

967

36.1

999

40.6

1033

45.2

1067

49.9

1103

55.0

44400 2416

907

27.9

923 29.8

953

33.6

984

37.7

1015

42.2

1047

46.9

1080

51.6

1113

56.7

45800 2493

927

29.4

942 31.5

972

35.5

1001

39.5

1032

43.9

1062

48.6

1094

53.5

1125

58.5

47200 2569

948

31.1

962 33.1

991

37.3

1019

41.3

1048

45.8

1078

50.5

1108

55.4

48600 2645

968

32.7

982 34.9

1010

39.2

1038

43.3

1066

47.7

1094

52.4

1123

57.4

50000 2721

988

34.5

1002 36.7

1030

41.1

1057

45.5

1084

49.8

1111

54.5

1139

59.5

51400 2798

1010

36.4

1023 38.6

1050

43.1

1076

47.7

1102

52.0

1129

56.7

52800 2874

1031

38.4

1043 40.6

1070

45.2

1095

49.9

1121

54.5

1146

59.0

54200 2950

1052

40.4

1064 42.7

1090

47.4

1115

52.1

1140

56.9

55600 3026

1074

42.6

1086 44.8

1110

49.5

1135

54.5

57000 3102

1096

44.8

1107 47.1

1130

51.9

58400 3179

1118

47.1

1129 49.5

1151

54.3

59800 3255

1140

49.5

1151 51.9

Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar).
Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses.
Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.