Constant Volume Dual-Duct
Calibration (3011)

This calibration procedure is used when
a constant volume of air must be
maintained through a unit. On a dual-
duct unit, a constant-volume discharge
sensor is used to measure the air
leaving the unit. The PVR controlling to a
constant-volume of air leaving the unit
uses the discharge sensor to maintain
the specified cfm.

This PVR does not require a thermostat
connected to the PVR.

The following procedure must be used
when calibrating a constant-volume
dual-duct unit. See Figure 15 for a
typical piping diagram.

1. Set t-stat to full heat.
2. Set LO thermostat (maximum) to the

desired maximum flow on the
heating deck.

3. Set t-stat to full cool.
4. Set HI thermostat (minimum) to

the desired minimum flow on the
heating deck.

5. Set LO thermostat adjustment knob

on cooling deck (CV deck) to desired
constant-volume.

6. Exercise the system to check flows

for proper operation.

Figure 15–Typical Constant-Volume
Dual-Duct Piping Diagram

Constant-Volume Dual-Duct
Calibration (3011)

Restrictor

Tee

(137.9)

20

S

20

(137.9)

S

20

(137.9)

S

Two-Pipe

Remote-Mounted

T-Stat

(Direct-Acting)

Actuator

HI

LO

Outlet

HI

LO

Constant-Volume

Flow Ring

Heating

Valve

g

Cooling

Valve

Normally-

Open

Normally-

Open

Volume

Regulator

Volume

Regulator

L

H

M

B

G

T

M

B

G

H

L

T

Actuator