Reversing relay – Trane VAV-SVX02B-EN User Manual

Page 5

Advertising
background image

5

VAV-SVX02B-EN

Reversing Relay

Calibration
By using the “bias” adjustment on the
relay, the factory-set 8.0–9.0 “cross-
over” can be changed. To recalibrate,
the relay should be connected as
illustrated in Figure 8.

Figure 8–Recalibrating Reversing Relay

If the new desired “cross-over”
pressure is 11.0 psi, this must be applied
to port #3 by adjusting the pressure
regulator. The “bias” adjustment is then
turned until 11.0 psi is obtained on the
output gage. Turning the “bias” adjust-
ment “CW” increases the output;
“CCW” decreases it.

This 11.0 psi “cross-over” would yield
the following operational chart:

Specifications
Maximum Pressure:
30 psig

Connections:
3/16" (4.& mm) nipples for ¼" (6.4 mm) OD
polyethylene tubing

Air Consumption:
0.5 SCFH (.236 L/M) @ 20 psig

Material:
ABS

Weight:
3 ½ oz

Chart

Input:

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

Output:

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

New Cross-over pressure

Bias

Adjustment

Screw

Gage

M

1

C

3

M

Pressure

Regulator

Ambient Limits:
+40°F/+120°F operating (+4°C/+49°C)

Mounting:
In-line via air connections

Factory Settings:
9 psig in./9 psig out and 8 psig in./8 psig
out

Bias Adjustment:
+/-15 psi