Thermostat, Thermostat selection and location – Trane VAV-SVX02B-EN User Manual

Page 2

Advertising
background image

VAV-SVX02B-EN

Thermostat Selection
and Location

In general, both one- and two-pipe
thermostats have a gain of 2.5 psi per
degree Fahrenheit, unless special
thermostats are used that provide a
different gain. The major difference
between them is that a one-pipe
thermostat is considered a low-
capacity thermostat and a two-pipe
thermostat is considered a high-
capacity thermostat.

When selecting between one-pipe and
two-pipe thermostats consider the
following:

Use one-pipe thermostat when:

— tubing runs are less than 50 feet from

thermostat to controller.

— a single thermostat will control no

more than three controllers.

— slower response is desired from the

thermostat.

Use two-pipe thermostat when:

— tubing runs exceed 50 feet from

thermostat to controller.

— a single thermostat will control four or

more controllers.

— high capacity air is required due to

restrictions in the air line.

Thermostat Piping
The two-pipe thermostat (Figure 1)
includes a restrictor (internally). Attach
supply air line and output pressure
(branch) line to the thermostat.

The one-pipe thermostat (Figure 2)
requires an external restrictor tee.
Connect main air supply to restricted
leg of restrictor tee. Connect branch line
from restrictor tee to the thermostat.

Figure 1–Two-Pipe Remote Thermostat (Reverse-Acting)

Thermostat

Figure 2–Typical One-Pipe Thermostat (Reverse-Acting)

2

Tee

20

(137.9)

15

(10

3.4

)

S

Two-Pipe

Remote-Mounted

T-Stat

(Reverse-Acting)

(137.9)

20

S

Tee

Restrictor

Tee

Restricted Leg

Fan
P.E.

Switch–1

(N.O.)

9 PSI

(62.06 kPa)

One-Pipe

Remote-Mounted

T-Stat

(Reverse-Acting)

Advertising