Danger, Description of terminals – Toshiba BCN002Z User Manual

Page 10

Advertising
background image

E6581402c

- 9 -

3.2. Description of terminals

<Control terminals specification>

Terminal

symbol

Function

Electrical specifications

Internal circuits

B

Communication signal (+)

A

Communication signal (-)

GND

Signal common

SCR

BACnet communication
signal
EIA-485

Shield terminal.
Connect to network ground.

B

A

GND

SCR

47k

47k

4.7k

4.7k

120

SW4

TERM

F

R

Multifunctional programmable
contact input.

SINK/SOURCE can be
selected with SW.

No voltage contact input
24V

DC

, 5mA or less

N.B. Use contact parts for low

current.

F, R

CC

P24

4.7k

P24

PTC

SOURCE

SINK

820

VIB

Multifunction programmable
analog input.
with internal pull-up resistor
for PTC

0 to 10V

DC

input

Using this terminal as PTC
input, set SW2 to PTC side
and set the parameters
(f645 and f646) to
proper value.

VIB

15k

VIB

P10

PTC

15k

3.3k

CC

Control circuit¶s equipotential

terminal

P24

24 V

DC

power supply output

24V

DC

-50mA

P24

P24

PTC

FLA
FLB

FLC

Multifunctional programmable
relay contact outputs

1c contact
30V

DC

-0.5A

250V

AC

-1A (cosI=1㧕

250V

AC

-0.5A (cosI=0.4)

FLA

FLB

FLC

Ry

Danger

Prohibited

Do not change switches settings while the power is on.

It may lead to electric shocks or damage.

Mandatory

Turn off the motor operation signals before setting the parameter and the switch
(SW), when changing the VIB function. Otherwise, the motor may suddenly start
and that may result in injuries.

Advertising