3.3. Network cable connection

Connect the BACnet network cable to communication option as follows.

Title

Description

Wire type

Shielded twisted cable

Characteristic impedance

Between 100 and 130 ohm

Distributed impedance between

conductors

Less than 100pF per meter

Distributed impedance between

conductors and shield

Less than 200pF per meter
Foil or braided shields are acceptable.

Length of an MSTP segment

1200 meters with AWG18 (0.8mm

2

)

Cable sheath should be peeled off by about 7mm.
For wiring work, use a flat blade screwdriver with a 0.6mm thick and
3.5mm width blade.
Tightening torque for the terminal block is 0.5Nm.

* Fix a cable so that a communication connector may be not taken the weight of wire.

3.4. Network configuration

Make up the network as follows.
- Transmission/reception signals (A, B)

Make up the communication path by connecting all transmission/reception data cables.

- Signal common (GND)

GND is the signal common.

- Grounding the shield of cable (SCR)

Connect the all shield lines of network cable. The shield shall be grounded at one end only prevent
currents from being created.

- Termination resistor

A termination resistance of 120 ohms plus or minus 5% shall be connected at each of the two ends
of the segment medium. This option has a termination resistor, so if use, set up the termination
resistor SW. (Refer to 2.1 Outline)
At least one set, and no more than two sets, of network bias resistors shall exist for each segment.
This option has local bias resistors.

Termination

B

A

GND

+5

510

510

Node with network

bias resistors

120

B

A

GND

Node without
bias resistors

B

A

GND

+5

47k

Node with local bias resistors

This option board

47k

4.7k

4.7k

Termination

120

SCR

Communication

cable

Communication

cable

SCR

SCR

SW4

TERM

N.B.:Do not connect the SCR terminal to the power ground of inverters or other units.

Keep the network cables 20cm or more separate from the power cables to prevent from
malfunctioning due to electromagnetic noise.