Wiring of a control terminal – Toshiba BCN002Z User Manual

Page 12

Advertising
background image

E6581402c

- 11 -

3.5. Wiring of a control terminal

Observe the following when wiring.

- Use 0.3 to 1.5mm

2

solid/stranded wire (AWG 22 to 16) for control cables.

- Remove the sheath of a cable about 7mm (6mm for FLA, FLB, FLC and G/E) from the end of cable.
- Use a flat-headed screwdriver with its blade 0.6mm in thickness and 3.5mm in width.
- Screw tightening torque for the terminal block screws should be 0.5 to 0.6Nm.

N.B.: Keep the control signal cables 20cm or more separate from the power cables to prevent from

malfunctioning due to electromagnetic noise.

N.B.: Provide an inter-lock system stated in below, when using a programmable controller that has

the open collector output.
When the programmable controller is turned off with the inverter is on, the difference between
each control power potential will cause wrong signals to the inverter as shown in below figure.
Provide an inter-lock so that the programmable controller cannot be turned off when the
inverter power is alive.

COM

+24V

Inverter

internal +24V

External

+24V supply

VF-FS1 + BCN002Z

Programmable controller

Input terminal

Fuse blowout
detection
circuit

Fuse