Warnings on refrigerant leakage, Check of concentration limit, Important – Toshiba MMK-AP0092H User Manual

Page 28

Advertising
background image

WARNINGS ON REFRIGERANT LEAKAGE

For the amount of charge in this example:

The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15kg.

NOTE 2 :

The standards for minimum room volume are as follows.

(1) No partition (shaded portion)

(2) When there is an effective opening with the adjacent

room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).

(3) If an indoor unit is installed in each partitioned room

and the refrigerant piping is interconnected, the
smallest room of course becomes the object. But
when a mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.

NOTE 3 :

The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows:
(When the ceiling is 2.7m high)

Check of Concentration Limit

The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its concentration will not
exceed a set limit.

The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws to be imposed
which protect the ozone layer. However, since it
contains more than air, it poses the risk of suffocation if
its concentration should rise excessively. Suffocation
from leakage of R410A is almost non-existent. With the
recent increase in the number of high concentration
buildings, however, the installation of multi air
conditioner systems is on the increase because of the
need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying
power etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of
the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure
so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event
of an emergency, measures can be made before injury
can occur).
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device.
The concentration is as given below.

Total amount of refrigerant (kg)

Min. volume of the indoor unit installed room (m³)

Concentration limit (kg/m³)

The concentration limit of R410A which is used in multi
air conditioners is 0.3kg/m³.

NOTE 1 :

If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.

Important

Outdoor unit

e.g.,
charged amount (15kg)

e.g., charged
amount (10kg)

Indoor unit

Room A Room B Room C Room D Room E Room F

Outdoor unit

Refrigerant piping

Indoor unit

Outdoor unit

Refrigerant piping

Indoor unit

Very

small

room

Small

room

Medium

room

Large room

Mechanical ventilation device - Gas leak detector

0

5

10

10

20

30

15

20

25

30

35

40

Range below the
density limit
of 0.3 kg/m³
(countermeasures
not needed)

Range above
the density limit
of 0.3 kg/m³
(countermeasures
needed)

Total amount of refrigerant

kg

Min.

indoor floor area

Advertising
This manual is related to the following products: