Tgu freezer controller settings, True food international equipment, inc – True Manufacturing Company TGU-2 User Manual

Page 14

Advertising
background image

............ www.truemfg.com ............

True Food International Equipment, Inc.

12

12

SCL

C

readout scale

SPL

-26

minimum set point

SPH

-12

maximum set point

SP

-21

set point

C-H

REF

mode (heat/cool)

HYS

3.5

differential

CRT

3

comp rest time

CT1

5

comp run fault probe 1

CT2

5

comp stop fault probe 1

CSD

30

comp stop delay with door open

DFM

RTC

defrost start mode

DFT

0

time interval for defrost

DH1

7

scheduled time for defrost

DH2

11

scheduled time for defrost

DH3

16

scheduled time for defrost

DH4

22

scheduled time for defrost

DH5

0

scheduled time for defrost

DH6

0

scheduled time for defrost

DLI

10

defrost end temperature

DTO

30

maximum defrost duration

DTY

ELE

defrost type (electric / gas)

DPD

20

evaporator pump down

DRN

2

pause after defrost (drain time)

DDM

DEF

defrost display mode

DDY

40

display delay

FID

NO

fans active during defrost

FDD

-2

evap fan restart temp after defrost

FTO

5

maximum evap fan stop after defrost

FCM

TIM

fan control mode (non/tmp/tim)

FDT

-0.8

evap-air temp diff for fans to stop

FDH

1.6

fan differential for fan re-start

FT1

30

fan stop delay after comp stop

FT2

4

timed fan stop

FT3

1

timed fan run

ATM

ABS

alarm (non/abs/rel)

ALA

-50

low temp alarm

AHA

-1

high temp alarm

ALR

0

low temp alarm differential

AHR

0

high temp alarm differential

ATI

T1

probe used for alarm

ATD

50

delay before alarm warning

ADO

30

delay before door alarm

AHM

ALR

operation for high cond alarm

AHT

65

condensation temp alarm

ACC

0

condenser period cleaning

IISM

NON

switchover mode for 2nd parameter

IISL

-250

minimum limit for IISP setting

IISH

250

maximum limit for IISP setting

IISP

-200

set point in mode 2

IIHY

40

differential in mode 2 (yes/no)

IIFC

NON

controller sensitivity for auto switchover

HDS

10

fan control in mode 2

IIDF

6

defrost timer set to start in defrost mode 2

SB

NO

standby button enabled (yes/no)

DS

NO

door switch

DI2

NON

digital input operation

STT

23.5

start time for timed actions

EDT

23.5

end time for timed actions

LSM

NON

light control mode (dor/man/non)

OA1

NON

aux 1 output operation

OA2

NON

aux 2 output operation

2CD

0

auxillary compressor start delay

INP

SN4

temp sensor probe selection

OS1

0

probe T1

T2

YES

probe T2 enabled (evap)

OS2

0

probe T2 offset

T3

NON

probe T3 operation

OS3

0

probe T3 offset

TLD

5

delay for min temp and max temp

SIM

3

display slowdown

ADR

1

address for PC communication

TGU FREEZER CONTROLLER SETTINGS

ALL OTHER SETTINGS ARE FACTORY PRE-SET AND SHOULD NOT BE CHANGED.

If you have any questions, please call TRUE technical service.

TRUE EUROPE • Fields End Road • Goldthorpe • NR, Rotherham • South Yorkshire UK
UK Office/Technical +44 (0) 1709 888 888 • UK Free Phone 0800 783 2049