Maintenance, Maintenance general information – Trane SCWH User Manual

Page 25

Advertising
background image

PKG-SVX14A-EN

25

Maintenance

general
information

Table M-GI-1. Midrange maintenance general data

SCWH030

SCWH050

SCWH075

SCWH100

SCWH120

SCWH150

dimensions, in-lbs.
height

66.93

78.74

78.94

91.54

95.47

95.47

length

31.89

36.41

40.94

65.75

65.75

80.31

depth

22.24

24.01

28.74

29.52

29.52

29.52

weight (shipping / net)

494 / 459

592 / 555

702 / 657

1094 / 1027 1133 / 1063

1249 / 1172

cooling performance
net cooling capacity, btu/h

36000

65290

87570

116986

138204

167303

EER

12.13

12.28

11.6

11.5

11.1

11.3

nominal air flow, cfm

1200

2000

3000

4000

4800

6000

system power, kW

3.0

5.3

7.6

10.2

12.5

14.8

Copeland scroll compressor
quantity

1

1

1

2

2

2

model

ZP32

ZP57

ZP83

ZP57

ZP67

ZP83

indoor coil, 3/8" tube size
face area, sq. ft.

3.19

4.98

7.13

12.12

12.12

14.56

rows / fpf

4 / 144

4 / 144

3 / 168

2 / 168

2 / 168

3 / 168

water condenser, tube & tube
water connection, in.

3/4 NPT

3/4 NPT

3/4 NPT

1 1/4 NPT

1 1/4 NPT

1 1/4 NPT

indoor fan, belt-driven
quantity

1

1

2

2

2

2

diameter x width

9 x 9

10 x 10

9 x 9

12 x 12

12 x 12

12 x 12

motor

1 / 0.5

1 / 1.0

1 / 2.0

1 / 2.0

1 / 3.0

1 / 3.0

motor frame size

56

56

56

56

56

56

air filter, 1" throwaway

size / (quantity), in.

14 x 25 (1)

14 x 20 (1) +

20 x 20 (1)

18 x 24 (2)

18 x 24 (3) +

24 x 24 (1)

refrigerant, R-410A, TXV control
refrigerant charge (Ckt 1 / 2), lbs.

3.8

5.4

7.8

5.1 / 5.2

6.5/6.3

7.2/7.2

hot water coil, 2-row, 108 fpf, 1/2" tubes
face area, sq. ft.

1.42

2.08

3.27

6.2

6.2

7.78

Notes:
1. Net cooling capacity is rated at 95°F ambient, 80°F entering dry bulb and 67°F entering wet bulb @ SCFM air condition.
2. EER is rated at ARI condition.

12 x 24 (1) + 24 x 24 (2)

Advertising
This manual is related to the following products: